Plan Review Notes
Plan Review Notes For Permit 22031357
Permit Number 22031357
Review Stop E
Sequence Number 1
Notes
Date Text
2022-04-05 13:11:59ELECTRIC REVIEW FAILED
 1) PLEASE EXPLAIN HOW THESE, THREE SEPARATE STRUCTURES,
 COMPLY WITH NEC 225.30,, BUILDING OR STRUCTURE SHALL BE
 SUPPLIED BY ONLY ONE FEEDER OR BRANCH CIRCUIT. IN
 ADDITION, SINCE THESE STRUCTURES APPEAR THAT THEY WILL
 REQUIRE AN ELECTRIC SUB PANEL, INDICATE THE NECESSARY
 GROUNDING ELECTRODE SYSTEM AS PER NEC 250.32
 2) PLEASE INCLUDE A NOTE, SEPERATE PERMITS REQUIRED FOR
 POOL, GENERATOR AND LOW VOLTAGE
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  