| Plan Review Notes For Permit 22031313 |
| Permit Number |
22031313 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2022-06-01 10:36:34 | ROOFING | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) WIND PRESSURES FOR THE ROOFING ARE SHOWN ON THE | | | "ROOF WIND LOADS" CHART (SHOULD SHOW FOR WIND ZONES 1G, | | | 1, 2 AND 3) - SEE FBC TABLE R301.2(2) - - FIGURE | | | R301.2(7)COMPONENT AND CLADDING PRESSURE ZONES | | | | | | 2) BUILDING DRAWING S2.1.H SHOWS A WIND PRESSURE OF | | | (-100) FOR ROOF WIND ZONE 3E - PRODUCT APPROVAL | | | FL14083-R27 ROOF SYSTEM NUMBER W-3 HAS A MAXIMUM WIND | | | DESIGN PRESSURE OF (-67.5) - PLEASE PROVIDE A LOW SLOPE | | | ROOFING SYSTEM THAT IS EQUAL OR HIGHER THAN THE | | | ALLOWABLE ROOF WIND DESIGN PRESSURE SHOWN ON THE | | | BUILDING DRAWING S2.1.H FOR ALL WIND ZONES. |
|