2022-04-26 12:56:20CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 22031205 2505 METROCENTRE BLVD W
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
 A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS
 REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW
 PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL
 PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST
 BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW
 APPROVAL.
  
 1. PLEASE NOTE FBC ACC 202.4.1, DISPROPORTIONATE COST:
 ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL TO THE ALTERED AREA WILL BE DEEMED
 DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE
 COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO THE
 PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS
 EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING
 AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE
 ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING
 RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS,
 ENLARGING TOILET STALLS, INSULATING PIPES, OR
 INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS
 ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH
 AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT,
 INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT
 TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING
 AN INACCESSIBLE DRINKING FOUNTAIN.
 ***A) PLEASE NOTE THE DRINKING FOUNTAIN LOCATION ON
 PLAN SHEET CS-1 AND THE REQUIREMENTS OF FBC ACC 307.2.
 OBJECTS WITH LEADING EDGES MORE THAN 27 INCHES AND NOT
 MORE THAN 80 INCHES ABOVE THE FINISH FLOOR OR GROUND
 SHALL PROTRUDE 4 INCHES MAXIMUM HORIZONTALLY INTO THE
 CIRCULATION PATH.
  
 2. PER WPB FBC 107.2.1, TO SHOW COMPLIANCE WITH FBC ACC
 CHAPTERS 2, 3 AND 6 PROVIDE PLAN AND ELEVATION DETAILS
 FOR NEW TOILET ROOM INDICATING THE FOLLOWING:
 ***A) IN ADDITION TO WHAT IS ALREADY SHOWN, PLEASE SHOW
 THE SIDE WALL GRAB BAR EXTENDING 54 INCHES MINIMUM FROM
 THE REAR WALL PER FBC ACC 604.5.1
 ***B) PLEASE NOTE THE DIMENSIONS OF THE CLEARANCE
 AROUND A WATER CLOSET; SHALL BE 60 INCHES MINIMUM
 MEASURED PERPENDICULAR FROM THE SIDE WALL AND 56 INCHES
 DEEP MINIMUM FOR WALL HUNG WATER CLOSETS AND 59 INCHES
 DEEP MINIMUM FOR FLOOR MOUNTED WATER CLOSETS MEASURED
 PERPENDICULAR TO THE REAR WALL PER FBC ACC 604.3.1 AND
 604.8.1.1.
 ***C) FLUSH CONTROLS SHALL BE LOCATED ON THE OPEN SIDE
 OF THE WATER CLOSET PER FBC ACC 604.6.
 ***D) PROVIDE DETAIL; URINALS SHALL BE THE STALL-TYPE
 OR THE WALL-HUNG TYPE WITH THE RIM 17 INCHES MAXIMUM
 ABOVE THE FINISH FLOOR OR GROUND. URINALS SHALL BE 13
 1/2 INCHES DEEP MINIMUM MEASURED FROM THE OUTER FACE OF
 THE URINAL RIM TO THE BACK OF THE FIXTURE PER FBC ACC
 605.2.
 ***E) MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS
 SHALL BE INSTALLED WITH THE BOTTOM EDGE OF THE
 REFLECTING SURFACE 40 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND PER FBC ACC 603.3. CLEARLY SHOW THE
 DIMENSION IS TO THE "REFLECTING" SURFACE OF THE MIRROR.
  
 3. PLAN SHEET P-1/PLUMBING FIXTURE SCHEDULE
 ***A) PER FBC PL 419.5, TEMPERED WATER SHALL BE
 DELIVERED THROUGH AN APPROVED WATER-TEMPERATURE
 LIMITING DEVICE THAT CONFORMS TO ASSE 1070 OR CSA
 B125.3, NOT ASSE 1016.
 ***B) SCHEDULED A.S. 3043.102 ELONGATED TOILET IS 1.1
 TO 1.6 GPF AND IS NAMED MADERA; THE CADET LINE OF WATER
 CLOSETS CONSISTS OF TANK TYPE AND THE MODEL NUMBER FOR
 AN ELONGATED HIGH EFFICIENCY (HET) WATER CLOSET WOULD
 BE 215.AB.104. PER WPB FBC 107.2.1, CLARIFY.
 ***C) SCHEDULED Z-6000XL-WS1 IS DISCONTINUED;
 REPLACEMENT Z6000-WS1-YB-YC PROVIDES 1.6 GPF. SCHEDULE
 CALLS FOR 1.28 GPF MAXIMUM FLOW RATE; PER WPB FBC
 107.2.1, CLARIFY. PLEASE NOTE Z-6000AV-HET PROVIDES
 1.28 GPF
 ***D) SCHEDULED Z-6003XL-WS1 IS NO LONGER NOTED IN ZURN
 PRODUCTS (ZURNPRODUCTS.COM). PER WPB FBC 107.2.1,
 REVIEW AVAILABLE PRODUCTS AND SELECT APPROPRIATE
 PRODUCT TO SUIT YOUR APPLICATION.
  
 4. PER FBC PL 604.1, THE DESIGN OF THE WATER
 DISTRIBUTION SYSTEM SHALL CONFORM TO ACCEPTED
 ENGINEERING PRACTICE. METHODS UTILIZED TO DETERMINE
 PIPE SIZES SHALL BE APPROVED.
 ***A) THE 1 INCH WATER SUPPLY TO EACH BATHROOM APPEARS
 TO BE UNDERSIZED. 12 WSFU/28.6 GPM (ONE EACH PUBLIC
 WC/FLUSHOMETER VALVE=10 WSFU; ONE PUBLIC LAVATORY HOT
 AND COLD TOTAL LOAD=2 WSFU) IS 10 FPS OR MORE (SEE FBC
 PL APPENDIX E/FIGURE E103.3(3) TYPE L COPPER TUBE,
 APPROXIMATELY 9 FPS (SEE FBC PL APPENDIX E/FIGURE
 E103.3(4) TYPE M COPPER TUBE. FBC PL APPENDIX E FIGURES
 E103.3(3) (4) STATES FLUID VELOCITIES IN EXCESS OF 5 TO
 8 FPS IS NOT USUALLY RECOMMENDED. PER WPB FBC 107.2.1,
 107.3.5.1.3 AND FBC PL 604.9, PROVIDE CALCULATIONS FOR
 SIZING OF WATER DISTRIBUTION. FBC PL APPENDIX E, SIZING
 OF WATER PIPING SYSTEM IS AN APPROVED METHOD.
 ***B) THE 3/4 INCH WATER SUPPLY TO THE TWO URINALS
 APPEARS TO BE UNDERSIZED; 10 WSFU/27 GPM. SEE FBC PL
 APPENDIX E FIGURES E103.3(3) (4).
  
 5. PER WPB FBC 107.2.1, PROVIDE A SCHEDULE INDICATING
 SIZING (PDI UNITS) AND MANUFACTURER. IDENTIFY WATER
 HAMMER ARRESTORS ON THE WATER RISER DIAGRAM INDICATING
 SIZE. PER FBC PL 604.9, WATER-HAMMER ARRESTORS SHALL
 CONFORM TO ASSE 1010.
  
 6. ALL COMPONENTS IN THE DOMESTIC WATER SYSTEM SHALL BE
 LEAD FREE IN ACCORDANCE WITH FBC PL 605.2 AND 605.2.1.
 PER WPB FBC 107.2.1, PROVIDE NOTE ON PLANS STATING THE
 SAME.
  
 7. HANGER DETAIL- PER WPB FBC 107.2.1, PROVIDE PIPE
 HANGER DETAIL WITH A NOTE STATING, "HORIZONTAL PIPE
 SHALL BE SUPPORTED IN ACCORDANCE WITH FBC PL TABLE
 308.5."
  
 8. PER WPB FBC 107.2.1, PROVIDE APPLICABLE RATED
 WALL/FLOOR DETAILS FOR PLUMBING PENETRATIONS COMPLYING
 WITH THE REQUIREMENTS OF FBC CHAPTER 7.
  
 9. PER WPB FBC 107.2.1, PROVIDE MANUFACTURER'S
 SPECIFICATION/INSTALLATION MANUAL FOR THE SCHEDULED
 WATER HEATER (SEE P-1/KEY NOTE 3) . PROVIDE ENERGY
 EFFICIENCY SHOWING COMPLIANCE WITH FBC EC TABLE C404.2.
  
 10. PER WPB FBC 107.2.1, PROVIDE A TRAP SEAL PROTECTION
 SPECIFICATION AND DETAIL FOR THE FLOOR DRAIN COMPLYING
 WITH ONE OF THE FOLLOWING: FBC 1002.4.1.1, 1002.4.1.2,
 1002.4.1.3 OR 1002.4.1.4.
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER PX928
 PLUMBING INSPECTOR BN2148
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  