| Plan Review Notes For Permit 22031205 |
| Permit Number |
22031205 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-04-14 12:57:35 | FIRE PROVISO COMMENTS: | | | EXISTING FIRE SPRINKLER AND FIRE ALARM SYSTEMS SHALL BE | | | MAINTAINED OPERABLE DURING DEMOLITION AND CONSTRUCTION. | | | ANY FIRE SPRINKLER AND/OR FIRE ALARM SYSTEM IMPAIRMENT | | | LASTING MORE THAN 4 CONSECUTIVE HOURS IN DURATION WILL | | | REQUIRE A FIRE WATCH TO BE IMPLEMENTED. | | | EXISTING FIRE SPRINKLER AND FIRE ALARM SYSTEMS SHALL BE | | | PROTECTED FROM DAMAGE DURING DEMOLITION AND/OR | | | CONSTRUCTION. | | | ALL FIRE SPRINKLER AND FIRE ALARM WORK SHALL BE | | | PERFORMED BY QUALIFIED CONTRACTORS. | | | WITH THE REMOVAL AND/OR ADDITION OF WALLS AND/OR | | | CEILINGS, ALL LIFE SAFETY SYSTEMS SHALL BE PROPERLY | | | EVALUATED FOR ADEQUATE COVERAGE AND EFFECTIVENESS. | | | |
|