Plan Review Notes
Plan Review Notes For Permit 22031205
Permit Number 22031205
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2022-04-14 12:57:35FIRE PROVISO COMMENTS:
 EXISTING FIRE SPRINKLER AND FIRE ALARM SYSTEMS SHALL BE
 MAINTAINED OPERABLE DURING DEMOLITION AND CONSTRUCTION.
 ANY FIRE SPRINKLER AND/OR FIRE ALARM SYSTEM IMPAIRMENT
 LASTING MORE THAN 4 CONSECUTIVE HOURS IN DURATION WILL
 REQUIRE A FIRE WATCH TO BE IMPLEMENTED.
 EXISTING FIRE SPRINKLER AND FIRE ALARM SYSTEMS SHALL BE
 PROTECTED FROM DAMAGE DURING DEMOLITION AND/OR
 CONSTRUCTION.
 ALL FIRE SPRINKLER AND FIRE ALARM WORK SHALL BE
 PERFORMED BY QUALIFIED CONTRACTORS.
 WITH THE REMOVAL AND/OR ADDITION OF WALLS AND/OR
 CEILINGS, ALL LIFE SAFETY SYSTEMS SHALL BE PROPERLY
 EVALUATED FOR ADEQUATE COVERAGE AND EFFECTIVENESS.
  