Plan Review Notes
Plan Review Notes For Permit 22031202
Permit Number 22031202
Review Stop Z
Sequence Number 2
Notes
Date Text
2022-08-29 14:38:43FAILED
  
 1) THE SUBMITTED COMMUNICATION FACILITY PLACEMENT
 PERMIT - CITY RIGHTS-OF-WAY (21091039) MUST BE APPROVED
 PRIOR TO THIS PERMIT BEING APPROVED. THE PLANS INCLUDED
 WITH THIS ELECTRICAL PERMIT MUST MATCH THE PLANS
 APPROVED WITH THE AFOREMENTIONED PERMIT. SOME OF THE
 COMMENTS BELOW ARE INCLUDED ON THE PLACEMENT PERMIT
 REVIEW AS WELL AS WITH THIS PERMIT.
  
 2) THE CITY CODE REQUIRES THAT POLES SHALL BE LOCATED
 SO AS TO ALIGN WITH EXISTING POLES IN THE RIGHT-OF-WAY
 AND HAVE EQUAL SETBACK DISTANCES WITH EXISTING POLES
 FROM THE CURBLINE OF THE RIGHT-OF-WAY. THE PROPOSED
 POLE IS NOT SHOWN IN LINE WITH THE EXISTING POWER POLES
 ALONG OKEECHOBEE ROAD. THE EXISTING POLES ARE LOCATED
 ADJACENT TO THE SIDEWALK. PLEASE ADJUST THE PROPOSED
 POLE LOCATION ACCORDINGLY.
  
 3) THE SURVEY SHOWS A 36-FOOT TALL UTILITY POLE ACROSS
 THE STREET FROM THE PROPOSED LOCATION TO SET THE
 FACILITY HEIGHT. THE 40.5-FOOT-TALL FACILITY SHOWN ON
 THE PLANS EXCEEDS THE CODE PERMITTED HEIGHT ALLOWANCE.
  
 4) THE PALM BEACH COUNTY ENGINEERING DETAILS NEED TO BE
 CHANGED TO THE CITY OF WEST PALM BEACH ENGINEERING
 DETAILS
  
 5) THE POLE STYLE MEETS CITY REQUIREMENTS. THE POLE
 COLOR AT THIS LOCATION SHALL BE RAL/RAYCAP 7042 TRAFFIC
 GREY A, OR EQUIVALENT.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
 [email protected]
  