| Plan Review Notes For Permit 22031125 |
| Permit Number |
22031125 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2022-06-06 10:17:51 | PREVIOUS COMMENT NOT ADDRESSED. PLAN STILL DETAILS 2/0 | | | CU CONDUCTORS FOR 200 AMP PANEL. THESE SHOULD BE | | | CORRECTLY SIZED AT 3/0 CU |
|