Plan Review Notes
Plan Review Notes For Permit 22031125
Permit Number 22031125
Review Stop E
Sequence Number 2
Notes
Date Text
2022-06-06 10:17:51PREVIOUS COMMENT NOT ADDRESSED. PLAN STILL DETAILS 2/0
 CU CONDUCTORS FOR 200 AMP PANEL. THESE SHOULD BE
 CORRECTLY SIZED AT 3/0 CU