Plan Review Notes
Plan Review Notes For Permit 22031125
Permit Number 22031125
Review Stop E
Sequence Number 1
Notes
Date Text
2022-04-25 11:46:41ELECTRIC REVIEW FAILED
 1) PLEASE DETAIL CORRECT SIZED 3/0 FEEDER CONDUCTOR FOR
 200-AMP ELECTRIC PANEL. NEC 310.15 (B)(7)(2) DOES NOT
 APPLY AS THESE FEEDER CONDUCTORS DO NOT SUPPLY THE
 ENTIRE LOAD OF THE DWELLING
 2) PLEASE DETAIL A CORRECTED LOAD CALCULATION FOR THE
 ENTIRE ELECTRIC SERVICE INCLUDING PANELS A, B, AND POOL
 PANEL BY CORRECTLY USING NEC 220..40 OR NEC 220.82
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  