| Plan Review Notes For Permit 22031107 |
| Permit Number |
22031107 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-03-23 12:58:09 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) THERE IS AN INDICATION OF NEW FLOORING BUT NO | | | INDICATION NOR SPEC SHEET FOR THE FLOOR | | | UNDERLAYMENT/SOUND PROOFING MATERIAL. | | | | | | PLEASE PROVIDE THE UNDERLAYMNET PRODUCT NAME AND SPEC | | | SHEETS. | | | | | | | | | | | | 2) THERE IS AN INDICATION OF THE FLOORING AS LVP AND | | | THERE IS A SPECIFICATION SHEET FOR SOME PRODUCT BUT NO | | | PRODUCT NAME NOR ONE ON THE SPEC SHEET THAT MATCH AND | | | CAN BE VERIFIED. | | | | | | LVP FLOORING MAY BE MANUFACTURED AROUND THE WORLD AND | | | NOT ALL ARE TESTED AND MEETING LISTED AND NFPA | | | STANDARDS. | | | | | | PER NFPA 101, CH 30 | | | | | | 30.3.3.3 INTERIOR FLOOR FINISH. | | | 30.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN | | | ACCORDANCE WITH | | | SECTION 10.2. | | | | | | 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH | | | 10.2.2.2 | | | ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL | | | HAVE A | | | MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2. | | | | | | FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE PRODUC | | | TNAME AND MATCHING SPEC SHEETS OF THE PROPOSED LVPL | | | FLOORING INDICATING THE FIRE BEHAVIOR RATING. | | | | | | | | | | | | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|