| Plan Review Notes For Permit 22031099 |
| Permit Number |
22031099 |
|
| Review Stop |
Z |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2022-05-31 13:29:32 | 5/31/2022 FAILED | | | | | | NEW SURVEY UPLOADED ON 5/27/2022 SHOWS GENERATOR TO BE | | | 5 FEET FROM PROPERTY LINES | | | | | | AND NEEDS TO BE 6 FEET AWAY FROM THE PROPERTY LINE TO | | | COMPLY WITH THE ZONING CODE: | | | | | | PURSUANT TO SECTION 94-305(B)(4) OF THE ZLDR: | | | MECHANICAL EQUIPMENT MAY NOT PROJECT MORE THAN 4 FEET | | | INTO A REQUIRED SETBACK. | | | | | | | | | VALENTINA BROGLIA | | | ASSOCIATE PLANNER | | | [email protected] | | | |
|