| 2022-05-31 10:41:58 | |
| | 1ST REVIEW FBC-2020 RES. GAS |
| | PERMIT- 22031099 |
| | 5/31/2022 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | NFPA 58 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) GAS RISER: THE MOST RECENT GAS PERMIT IN THE WPB |
| | BUILDING DEPARTMENT RECORDS THAT SHOWED THE FULL BTU |
| | LOAD OF ALL GAS-FIRED APPLIANCES WAS PERMIT- 05081958. |
| | THE GAS ISOMETRIC ON FILE SHOWS A TOTAL BTU LOAD OF |
| | 920,000 WHICH INCLUDED A 400,000 BTU POOL HEATER. |
| | PLEASE REVISE THE GAS RISER TO INCLUDE THE FOLLOWING |
| | INFORMATION PER NFPA 58: |
| | A) TOTAL BTU LOAD OF THE SYSTEM AND INDIVIDUAL |
| | APPLIANCE BTU LOADS. PLEASE NOTE THE GENERATOR SPECS |
| | SHOW A 340,000 BTU LOAD FOR THE GENERATOR. |
| | B) SHOW THE TANK LOCATION AND THE TOTAL DEVELOPED |
| | LENGTH OF THE SYSTEM FROM THE TANK TO THE MOST REMOTE |
| | APPLIANCE OUTLET. |
| | C) BRANCH AND CUT PIPE LENGTH MEASUREMENTS. |
| | D) TYPES AND SIZES OF GAS PIPING. |
| | E) LOCATIONS OF REGULATORS AND THE INPUT AND OUTPUT |
| | PRESSURES. |
| | F) PIPE SIZING TABLES. |
| | |
| | 2) THE GAS RISER SHALL BEAR THE PRINTED NAME, LICENSE |
| | NUMBER AND SIGNATURE OF THE GAS PIPING INSTALLATION |
| | CONTRACTER OR QUALIFIER WHO PREPARED THE DRAWING- SEC. |
| | 107.2.1 WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |