| 2022-03-23 12:32:41 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | 1) THERE IS AN INDICATION OF THE SPEC SHEET FOR THE |
| | FLOOR UNDERLAYMENT, BUT NO SPEC SHEET NOR A PRODUCT |
| | NAME FOR THE ACTUAL PROPOSED TILE FLOORING. |
| | |
| | PER SHEET PROP COND UNDER FLOOR FINISH IT INDICATES |
| | WITHIN THE MODEL NAME/NUMBER COLUMN FLOOR FINISH T.B.D. |
| | AND UNDER THE FIRE PERFORMANCE COLUMN INDICATES A |
| | CRITICAL RADIANT FLUX BUT ALSO A FIRE RESISTIVE WALL, |
| | WHICH IS NOT APPLICABLE. |
| | |
| | TILE FLOORING MAY HAVE DIFFERENT TYPE |
| | MEANINGS/DEFINITIONS AND IS MANUFACTURED AROUND THE |
| | WORLD AND NOT ALL ARE TESTED AND MEETING LISTED AND |
| | NFPA STANDARDS. |
| | |
| | PER NFPA 101, CH 30 |
| | |
| | 30.3.3.3 INTERIOR FLOOR FINISH. |
| | 30.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN |
| | ACCORDANCE WITH |
| | SECTION 10.2. |
| | |
| | 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH |
| | 10.2.2.2 |
| | ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL |
| | HAVE A |
| | MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2. |
| | |
| | FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE FLOORING |
| | PRODUCT NAME AND THE PRODUCT SPEC SHEETS OF THE |
| | PROPOSED FINISHED FLOORING INDICATING THE FIRE BEHAVIOR |
| | RATING. |
| | |
| | IF THE PROPOSED FLOORING IS PORCELAIN/CERAMIC TILE, |
| | NATURAL STONE TILE, CONCRETE TILES, PRODUCT SPEC SHEETS |
| | WOULD NOT BE REQUIRED. |
| | |
| | PRODUCT SPEC SHEETS ARE REQUIRED FOR LVT, VINYL |
| | FLOORING, WOOD/VINYL LAMINATES, ETC. |
| | |
| | |
| | 2) THERE ARE INDICATIONS OF BATHROOM TUB WORK IN TH |
| | MASTER BATH THAT MAY AFFECT THE FIRE RATED |
| | TENANT/CORRIDOR SEPARATION WALLS, |
| | |
| | ENSURE FIRE RATED TENANT SEPARATION WALLS ARE REPAIRED |
| | TO THE EXISTING FIRE RATED SEPARATION. |
| | |
| | PROVIDE AN APPLICABLE NOTE OF ACKNOWLEDGMENT. |
| | |
| | |
| | |
| | 3) THERE ARE INDICATIONS OF REMOVING A WALL IN THE |
| | KITCHEN/LIVING AREA. |
| | |
| | REMOVAL OF WALLS REQUIRES A CODE COMPLIANT SPRINKLER |
| | HEAD COVERAGE REVIEW BY A FIRE SPRINKLER CONTRACTOR. |
| | |
| | ALL FIRE SPRINKLER WORK SHALL BE DONE UNDER SEPARATE |
| | PERMIT AND SHOP DRAWINGS. |
| | |
| | PROTECT FIRE SPRINKLERS AND FIRE ALARM DEVICES AND |
| | EQUIPMENT. |
| | |
| | DO NOT PAINT OVER SPRINKLER HEADS AND/OR FIRE ALARM |
| | DEVICES/EQUIPMENT. |
| | |
| | THE FS AND FA SYSTEMS SHALL BE MAINTAINED THROUGHOUT |
| | DEMO AND CONSTRUCTION. |
| | |
| | PLEASE REVIEW, ENSURE COMPLIANCE AND PROVIDE A NOTE OF |
| | ACKNOWLEDGEMENT ON THE FLOOR PLAN. |
| | |
| | |
| | |
| | |
| | 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |