Plan Review Notes
Plan Review Notes For Permit 22031012
Permit Number 22031012
Review Stop E
Sequence Number 1
Notes
Date Text
2022-04-13 22:14:02ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. ELECTRICAL NOTE #1 IS INCORRECT. FLORIDA STATUTE
 471.003 (2) (H) (1 AND 2A) READS AS FOLLOWS:
  
 (H)?ANY ELECTRICAL, PLUMBING, AIR-CONDITIONING, OR
 MECHANICAL CONTRACTOR WHOSE PRACTICE INCLUDES THE
 DESIGN AND FABRICATION OF ELECTRICAL, PLUMBING,
 AIR-CONDITIONING, OR MECHANICAL SYSTEMS, RESPECTIVELY,
 WHICH SHE OR HE INSTALLS BY VIRTUE OF A LICENSE ISSUED
 UNDER CHAPTER 489, UNDER FORMER PART I OF CHAPTER 553,
 FLORIDA STATUTES 2001, OR UNDER ANY SPECIAL ACT OR
 ORDINANCE WHEN WORKING ON ANY CONSTRUCTION PROJECT
 WHICH:
 1.?REQUIRES AN ELECTRICAL OR PLUMBING OR
 AIR-CONDITIONING AND REFRIGERATION SYSTEM WITH A VALUE
 OF $125,000 OR LESS; AND
 2.A.?REQUIRES AN AGGREGATE SERVICE CAPACITY OF 600
 AMPERES (240 VOLTS) OR LESS ON A RESIDENTIAL ELECTRICAL
 SYSTEM OR 800 AMPERES (240 VOLTS) OR LESS ON A
 COMMERCIAL OR INDUSTRIAL ELECTRICAL SYSTEM
  
 THEY ARE NOT REQUIRED TO TAKE RESPONSIBILTY FOR THE
 DESIGN, THEY ARE EXEMPT FROM NEEDING A DESIGN
 PROFESSIONAL TO DESIGN THE DRAWINGS IF THEY CHOOSE.
 PLEASE PROVIDE CORRECTION IF YOU WISH TO KEEP NOTE ON
 PLAN.
  
 2. ELECTRICAL NOTE #19 IS INCORRECT. IT IS 90% OF LIGHT
 FIXTURES IN THE CURRENT ADOPTED ENERGY CODE FBC-EC 2020
 7TH EDITION FBC-EC R404.1 PLEASE PROVIDE CORRECTION.
  
 3.RECEPTACLE REQUIRED ON BALCONY PER NEC 210.52E3
 PLEASE PROVIDE CORRECTION.
  
 4. ELECTRICAL PLAN IS REQUIRED TO BE DESIGNED AND
 SIGNED/SEALED BY A DESIGN PROFESSIONAL OR SIGNED BY THE
 ELECTRICAL CONTRACTOR QUALIFIER. PROVIDE CORRECTION. FS
 471.003(2)(H); 471.025; WPB FBC 107.1
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  