| Plan Review Notes For Permit 22030951 |
| Permit Number |
22030951 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-04-07 11:23:27 | BUILDING REVIEW COMMENTS: | | | | | | W.P.B. PERMIT: 22030951 | | | REVIEWED: APRIL 7, 2022 | | | | | | DYLAN BATTLES | | | BUILDING PLANS EXAMINER PX4191 | | | [email protected] | | | 561-805-6718 | | | | | | FLORIDA BUILDING CODE,6TH EDITION (2017) | | | FBC[AMENDED] = 2020 CHAPTER 1 WPB AMENDMENTS (SEE LINK | | | BELOW) | | | HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/ | | | BUILDING-PERMIT-FORMS | | | FBC[B] = FBC BUILDING | | | FBC[EXISTING] = FBC EXISTING BUILDING | | | | | | 1. PLEASE PROVIDE REPORTS FOR THE BRAND OF UNDERLAYMENT | | | FOR STC AND IIC | | | | | | 1207.2 FBC[B] AIR-BORNE SOUND. WALLS, PARTITIONS AND | | | FLOOR/CEILING ASSEMBLIES SEPARATING DWELLING UNITS AND | | | SLEEPING UNITS FROM EACH OTHER OR FROM PUBLIC OR | | | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS OF | | | NOT LESS THAN 50, OR NOT LESS THAN 45 IF FIELD TESTED, | | | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM | | | E90. | | | | | | 1207.3 FBC[B] STRUCTURE-BORNE SOUND. FLOOR/CEILING | | | ASSEMBLIES BETWEEN DWELLING UNITS AND SLEEPING UNITS OR | | | BETWEEN A DWELLING UNIT OR SLEEPING UNIT AND A PUBLIC | | | OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN | | | IMPACT INSULATION CLASS RATING OF NOT LESS THAN 50, OR | | | NOT LESS THAN 45 IF FIELD TESTED, WHEN TESTED IN | | | ACCORDANCE WITH ASTM E492. | | | | | | | | | PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F | | | 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME | | | [email protected] | | | | | | | | | |
|