| 2022-04-06 22:22:12 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. ELECTRICAL PLAN IS REQUIRED TO BE SIGNED BY THE |
| | ELECTRICAL CONTRACTOR QUALIFIER. PROVIDE CORRECTION. FS |
| | 471.003(2)(H); 471.025; WPB FBC 107.1 |
| | |
| | 2. PLAN UPLOADED IS NOT CLEAR AND IS UNABLE TO BE |
| | REVIEWED. PLEASE UPLOAD PLAN AGAIN OR SEND PLAN |
| | DIRECTLY TO [email protected] |
| | |
| | 107.2.1.3 QUALITY OF BUILDING PLANS. BUILDING PLANS |
| | SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON |
| | SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM. |
| | THE BUILDING OFFICIAL MAY ESTABLISH THROUGH |
| | DEPARTMENTAL POLICY, OTHER STANDARDS FOR PLANS AND |
| | SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO ITS |
| | RECORD RETENTION PROGRAM. THIS POLICY MAY INCLUDE SUCH |
| | THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, OR |
| | OTHER ITEMS RELATED TO RECORDS MANAGEMENT. ELECTRONIC |
| | MEDIA MUST BE COMPATIBLE WITH THE ARCHIVE REQUIREMENTS |
| | OF FLORIDA STATUTES. |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | CODES IN EFFECT: |
| | |
| | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B |
| | UILDING-PERMIT-FORMS |
| | |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2020 7TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| | 7TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | FRANK GIAQUINTO III |
| | ELECTRICAL INSPECTOR |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | [email protected] |
| | CELL: 561-805-6744 |
| | |
| | |
| | ELECTRICAL PLAN IS REQUIRED TO BE DESIGNED AND |
| | SIGNED/SEALED BY A DESIGN PROFESSIONAL OR SIGNED BY THE |
| | ELECTRICAL CONTRACTOR QUALIFIER. PROVIDE CORRECTION. FS |
| | 471.003(2)(H); 471.025; WPB FBC 107.1 |