| Plan Review Notes For Permit 22030918 |
| Permit Number |
22030918 |
|
| Review Stop |
G |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2022-08-19 09:52:31 | 1ST GAS REVIEW | | | | | | V7 FPC - 2020 FLORIDA PLUMBING CODE | | | V7 FGC - 2020 FLORIDA FUEL GAS | | | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE | | | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE | | | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE | | | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION | | | 2021 F.S. - 2021 FLORIDA STATUTES | | | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE | | | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE | | | FBC CHAPTER 1 | | | | | | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED | | | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. | | | | | | 1. 2020 FRC G2439.5 - PLEASE SHOW THE MAKE | | | UP/COMBUSTION AIR CALCS REQUIRED FOR THE GAS DRYER. | | | | | | 2. 2017 WPB AMENDS 107.2.1 - THE PLANS SHOW AN ATS FOR | | | A GENERATOR AND THE GENERATOR DOES NOT APPEAR TO BE ON | | | THE GAS RISER, PLEASE CLARIFY. | | | | | | 3. 2020 FRC G2413.3 - THE GAS DIAGRAM DOES NOT SHOW ANY | | | PIPE LENGTHS. PLEASE INDICATE THE LENGTHS USED, SYSTEMS | | | PRESSURES, AND GAS TABLES USED FOR PIPE SIZING. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | | | | RYAN W. BROWN | | | CHIEF PLUMBING INSPECTOR | | | OFFICE: 561-805-6692 | | | CELL: 561-517-4293 | | | EMAIL: [email protected] | | | |
|