| Plan Review Notes For Permit 22030871 |
| Permit Number |
22030871 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2022-04-13 09:13:41 | PETER E VALENTI | | | BUILDING PLANS EXAMINER II | | | [email protected] | | | 561 805 6673 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC M = FBC MECHANICAL | | | FBC FG = FBC FUEL GAS | | | | | | BUILDING REVIEW DENIED: | | | THE FOLLOWING ITEMS ARE REQUIRED PRIOR TO ISSUANCE OF A | | | DEMO PERMIT PER FLORIDA BUILDING | | | CODE, BUILDING 3303: | | | | | | | | | WATERDOWN METHOD: | | | IF A WATER TRUCK IS DESIRED, PROVIDE DETAILED | | | INFPRMATION OF THE WATER TRUCK SUCH AS: THE | | | GALLON CAPACITY OF THE WATER TANK AND A LETTER | | | INCLUDING A STATEMENT THAT THE WATER | | | USED WILL BE POTABLE AND FROM AN OFF?SITE LOCATION ONLY | | | AND WILL BE ON?SITE AT ALL TIMES | | | DURING DEMOLITION. | | | IF A HYDRANT METER OR BACKFLOW PREVENTER IS DESIRED, | | | THEN A PARTIAL RELEASE WILL BE NOTED | | | ON THEIR FORM. IF THE BACKFLOW PREVENTER DEVICE IS | | | SELECTED, A PLUMBING PERMIT IS REQUIRED. BEFORE | | | SCHEDULING THE 703(PLUMBING FINAL INSPECTION), THE | | | BACKFLOW DEVICE NEEDS TO BE TESTED AND CERTIFIED BY | | | THE CITY?S UTILITIES DEPT, 561?822?2244. FAX THE | | | COMPLETED "DEMOLITION APPLICATION" FORM TO | | | 561?822?2183. | | | 4. SEWER LATERAL CAPPING PERMIT IS REQUIRED (SUBMIT | | | APPLICATION TO BUILDING DIVISION); | | | SCHEDULE A FINAL PLUMBING #703. | | | |
|