2022-04-12 11:47:50CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 22030798 4500 S DIXIE HWY
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
  
 A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS
 REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW
 PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL
 PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST
 BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW
 APPROVAL.
  
 1.RE: A-4.10
 ***A) DIMENSION SHALL BE TO THE BOTTOM EDGE OF
 "REFLECTING SURFACE" PER FBC ACC 603.3.
 ***B) THE SIDE WALL GRAB BAR SHALL BE 42 INCHES LONG
 MINIMUM, LOCATED 12 INCHES MAXIMUM FROM THE REAR WALL
 AND EXTENDING 54 INCHES MINIMUM FROM THE REAR WALL PER
 FBC ACC 604.5.1. PLEASE NOTE THE OVERALL DIMENSION OF
 54 INCHES MINIMUM FROM THE REAR WALL.
 ***C) PER WPB FBC 107.2.1, PLEASE NOTE DIMENSIONS OF
 CLEARANCE AROUND THE WATER CLOSET(S); SHALL BE 60
 INCHES MINIMUM MEASURED PERPENDICULAR FROM THE SIDE
 WALL AND 56 INCHES DEEP MINIMUM FOR WALL HUNG WATER
 CLOSETS AND 59 INCHES DEEP MINIMUM FOR FLOOR MOUNTED
 WATER CLOSETS MEASURED PERPENDICULAR TO THE REAR WALL
 PER FBC ACC 604.3.1 AND 604.8.1.1.
 ***D) URINALS SHALL BE 13 1/2 INCHES DEEP MINIMUM
 MEASURED FROM THE OUTER FACE OF THE URINAL RIM TO THE
 BACK OF THE FIXTURE PER FBC ACC 605.2
  
 2.PLAN SHEET P-4:
 ***A) PER WPB FBC 107.2.1, PLEASE LOCATE AND IDENTIFY
 ON THE PLAN, THE EXISTING WATER HEATER.
 ***B) ADD TO KEY NOTES THE FOLLOWING STATEMENT; "IF THE
 DEVELOPED LENGTH OF HOT OR TEMPERED WATER PIPING, FROM
 THE SOURCE OF HOT WATER TO THE FIXTURES THAT REQUIRE
 HOT OR TEMPERED WATER, EXCEEDS 50 FEET, A RECIRCULATING
 SYSTEM OR HEAT-TRACED SYSTEM SHALL BE INSTALLED TO
 PROVIDE COMPLIANCE WITH THE FLORIDA PLUMBING CODE
 SECTION 607.2."
 ***C) ADD TO THE KEY NOTES THE FOLLOWING STATEMENT:
 "PER THE WEST PALM BEACH AMENDMENTS SECTION 107.4, IF A
 NEW WATER HEATER AND/OR A NEW HOT WATER RECIRCULATING
 OR HEAT-TRACE SYSTEM IS REQUIRED, A PLAN REVISION SHALL
 BE SUBMITTED THE BUILDING DEPARTMENT FOR APPROVAL.
 APPROVED REVISION SHALL BE ON SITE FOR FINAL
 INSPECTION."
  
 3.ALL COMPONENTS IN THE DOMESTIC WATER SYSTEM SHALL BE
 LEAD FREE IN ACCORDANCE WITH FBC PL 605.2 AND 605.2.1.
 PER WPB FBC 107.2.1, PROVIDE NOTE ON PLANS STATING THE
 SAME.
  
 4. PER WPB FBC 107.2.1, PROVIDE PIPE HANGER DETAIL WITH
 A NOTE STATING, "HORIZONTAL PIPE SHALL BE SUPPORTED IN
 ACCORDANCE WITH FBC PL TABLE 308.5."
  
 5. PER WPB FBC 107.2.1, PROVIDE A SLAB REPAIR DETAIL ON
 THE PLANS. SHOW THE WIDTH OF THE REPAIR, THE MINIMUM
 THICKNESS AND PSI OF THE CONCRETE TO BE REPLACED. SHOW
 SIZE, LENGTH, SPACING (ON CENTER), MINIMUM EMBEDMENT
 AND ANCHORING/ADHESIVE MATERIAL FOR DOWELS. THE REPAIR
 SHALL ALSO INCLUDE TERMITE TREATMENT OF THE SOIL AS
 WELL AS THE REQUIRED VAPOR BARRIER OVER WELL COMPACTED
 SOIL. A COPY OF THE TERMITE CERTIFICATE SHALL BE ONSITE
 FOR FINAL INSPECTION. WPB FBC 105.11
  
 6. P301 AND P601: THE FOUR NEW SANITARY DRAINS EXITING
 THE BUILDING EACH CONSTITUTE AN INDIVIDUAL BUILDING
 DRAIN AS DEFINED IN FBC PL CHAPTER 2, SECTION 202. PER
 FBC PL 708.1.3, PROVIDE A CLEANOUT ON EACH BUILDING
 DRAIN TO SERVICE THE JUNCTION OF THE BUILDING DRAIN AND
 BUILDING SEWER.
  
 7.P801: PER WPB FBC 107.2.1, PROVIDE A FIXTURE
 SCHEDULE/SPECIFICATION LISTING MANUFACTURER, MODEL
 NUMBER, TRIM.
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  