Plan Review Notes
Plan Review Notes For Permit 22030777
Permit Number 22030777
Review Stop B
Sequence Number 3
Notes
Date Text
2022-06-30 11:12:473RD BUILDING REVIEW
  
 1) THE PREVIOUS (2ND) REVIEW COMMENT HAS NOT BEEN
 COMPLETELY ADDRESSED. THE CALCULATIONS ON THE PLAN
 INDICATE A B EXPOSURE , THE PROPERTY IS IN A C
 EXPOSURE- SEE COMMENT BELOW, AND NOTE THAT THE PLAN WAS
 ALSO FAILED FOR ELECTRONIC SIGNATURE- SEE SIGNATURE
 COMMENT.
  
 CHRISTOPHER COLE
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6719
  
 ****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 3. FBC R 301, THIS INSTALLATION IS OUTDOORS. REVISE
 PLAN TO INCLUDE WIND DESIGN CRITERIA.
  
 THIS APPEARS TO BE 170MPH, EXPOSURE C.
  
  
  