| Plan Review Notes For Permit 22030777 |
| Permit Number |
22030777 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-05-14 14:11:24 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 1. FBC 107, PLANS ARE TO BE ARCHITECTURAL QUALITY, | | | DRAWN TO SCALE. PROVIDE A BASIC FLOOR PLAN SHOWING THE | | | EXISTING COVERED PATIO, LABELED AS SUCH, WITH PROPOSED | | | IMPROVEMENTS DRAWN TO SCALE WITH DIMENSIONS. | | | | | | 2. FBC 107, IT APPEARS THAT THE PROPANE TANK WILL BE | | | INSTALLED INSIDE THE CABINET. WILL THE CABINET HAVE | | | VENTILATION? PLEASE SEE THE INSTALLATION INSTRUCTIONS | | | FOR THE PROPANE TANK FOR FURTHER INFORMATION. | | | | | | 3. FBC R 301, THIS INSTALLATION IS OUTDOORS. REVISE | | | PLAN TO INCLUDE WIND DESIGN CRITERIA. | | | | | | 4. THE PLAN SHOULD INCLUDE THE PRINTED NAME AND | | | SIGNATURE OF THE INDIVIDUAL TAKING RESPONSIBILITY FOR | | | THE DESIGN. INCLUDE GOVERNING CODE (FBC 2020, | | | RESIDENTIAL). | | | | | | |
|