| Plan Review Notes For Permit 22030774 |
| Permit Number |
22030774 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-03-18 11:20:21 | FIRE PROVISO COMMENTS: | | | DUCT DETECTORS SHALL GENERATE A SUPERVISORY ALARM AT | | | THE FIRE CONTROL PANEL AND THE REMOTE ANNUNCIATOR | | | PANEL. NFPA 72, 2016, 21.7.4 | | | 24 HOUR BATTERY TESTING MAY BE REQUIRED TO BE WITNESSED | | | BY AN INSPECTOR FROM THE WEST PALM BEACH FIRE | | | DEPARTMENT TO INSURE OPERATIONAL COMPLIANCE WITH NFPA | | | 72 2016, TABLE 14.4.3.2 | | | |
|