Plan Review Notes
Plan Review Notes For Permit 22030774
Permit Number 22030774
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2022-03-18 11:20:21FIRE PROVISO COMMENTS:
 DUCT DETECTORS SHALL GENERATE A SUPERVISORY ALARM AT
 THE FIRE CONTROL PANEL AND THE REMOTE ANNUNCIATOR
 PANEL. NFPA 72, 2016, 21.7.4
 24 HOUR BATTERY TESTING MAY BE REQUIRED TO BE WITNESSED
 BY AN INSPECTOR FROM THE WEST PALM BEACH FIRE
 DEPARTMENT TO INSURE OPERATIONAL COMPLIANCE WITH NFPA
 72 2016, TABLE 14.4.3.2
  