| 2022-05-03 15:58:58 | PLUMBING AUDIT |
| | PERMIT- 22030685 |
| | 5/3/22 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) IA110, IA-801 OR P2.1: CLEAR FLOOR SPACE DIAGRAMS W/ |
| | DIMENSIONS AT THE ACCESSIBLE SINK, DISHWASHER, AND |
| | REFRIGERATOR NOT PROVIDED- SEC. 606.2 & 804.6 FBC ACC. |
| | |
| | 2) IA-801: PANTRY EQUIPMENT ITEM #8 NOT SHOWN IN THE |
| | SCHEDULE- SEC. 107.2.1 WPB. |
| | |
| | 2) P0.1: LOCATION OF THE REQUIRED DEDICATED SHUT OFF |
| | VALVE FOR THE IWH UNDER THE SINK NOT SHOWN- SEC 503.1 |
| | FBC P. |
| | |
| | 3) P0.1: PUBLIC LAVATORY LABELING AT THE SINK DETAIL |
| | INCORRECT. ACCORDING TO THE PLANS THE SINK IS IN THE |
| | PANTRY- SEC. 107.2.1 WPB. |
| | |
| | 4) P0.1: HOT WATER, NOT TEMPERED WATER IS REQUIRED AT |
| | THE PANTRY SINK. REMOVE THE TEMPERED WATER MIXING VALVE |
| | AND ALL REFERENCES TO TEMPERED WATER- SECS 419.5 AND |
| | 607.1.2 FBC. PROVIDE A MIXING VALVE THAT WILL LIMIT THE |
| | HOT WATER TEMPERATURE IN ACCORDANCE WITH SEC. 607.1.1. |
| | |
| | 5) P2.1: INSTALLATION OF THE NEW DRAINS WILL REQUIRE |
| | THE FLOOR TO BE X-RAYED TO IN ORDER TO LOCATE |
| | REINFORCING STEEL OR POST STRESSED FLOOR TENDONS. |
| | PLEASE PLACE A NOTE ON THE PLANS TO VERIFY COMPLIANCE |
| | WILL BE MET- SECTION 107.2.1 WPB. |
| | |
| | 6) P2.1: NEW DRAIN PIPE PENETRATIONS OF THE EXISTING |
| | SLAB WILL REQUIRE FIRESTOPPING TO SEAL THE ANNULAR |
| | SPACE AROUND THE PIPING. PROVIDE A UL TESTED AND |
| | APPROVED FIRESTOPPING ASSEMBLY DETAIL ON THE PLAN- |
| | SECTION 315.1 FBC P AND SECTION 714.4.1.2 FBC B. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |