Plan Review Notes
Plan Review Notes For Permit 22030685
Permit Number 22030685
Review Stop M
Sequence Number 1
Notes
Date Text
2022-05-03 10:37:201ST REVIEW FMC
 PERMIT: 22030685
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE OUTSIDE AIR CALCULATIONS NOTE 1 INDICATES THE
 CALCULATIONS ARE BASED ON ESTIMATED MAX. OCCUPANCY
 RATES PER ARCHITECTURAL PLANS AND MECHANICAL FBC 2020
 CH-4; VENTILATION RATES PER MECHANICAL FBC 2017 CH-4.
 SOME OF THE AREAS HAVE A LOW OUTDOOR AIR CALCULATION.
 PLEASE CHANGE THE REFERENCE TO THE 2017 CODE AS WE ARE
 CURRENTLY IN THE 2020 FMC. ALSO REMOVE AND DO NOT USE
 THE ARCHITECTURAL ESTIMATED MAX. OCCUPANCY AS THE 2020
 FMC 403.3.1.1 3RD SENTENCE STATES: THE OCCUPANT LOAD
 UTILIZED FOR DESIGN OF THE VENTILATION SYSTEM SHALL BE
 NOT LESS THAN THE NUMBER DETERMINED FROM THE ESTIMATED
 MAXIMUM OCCUPANT LOAD RATE INDICATED IN TABLE
 403.3.1.1.
  
 2) SHEET M2.1: WHERE IS THE DETAIL SHOWING WHAT KEYNOTE
 1 IS ASKING FOR? IS THIS NEW DUCTWORK IN A SHAFT? FBC
 107.2.1
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  