| 2022-05-03 10:37:20 | 1ST REVIEW FMC |
| | PERMIT: 22030685 |
| | |
| | CODES IN EFFECT: 2020 |
| | |
| | FBC- FLORIDA BUILDING CODE |
| | FMC- FLORIDA MECHANICAL CODE |
| | FEC- FLORIDA ENERGY CONSERVATION |
| | FGC- FLORIDA FUEL GAS |
| | FEX- FLORIDA EXISTING BUILDING CODE |
| | FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| | F.S.- FLORIDA STATUTES |
| | FAC- FLORIDA ACCESSIBILITY CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE OUTSIDE AIR CALCULATIONS NOTE 1 INDICATES THE |
| | CALCULATIONS ARE BASED ON ESTIMATED MAX. OCCUPANCY |
| | RATES PER ARCHITECTURAL PLANS AND MECHANICAL FBC 2020 |
| | CH-4; VENTILATION RATES PER MECHANICAL FBC 2017 CH-4. |
| | SOME OF THE AREAS HAVE A LOW OUTDOOR AIR CALCULATION. |
| | PLEASE CHANGE THE REFERENCE TO THE 2017 CODE AS WE ARE |
| | CURRENTLY IN THE 2020 FMC. ALSO REMOVE AND DO NOT USE |
| | THE ARCHITECTURAL ESTIMATED MAX. OCCUPANCY AS THE 2020 |
| | FMC 403.3.1.1 3RD SENTENCE STATES: THE OCCUPANT LOAD |
| | UTILIZED FOR DESIGN OF THE VENTILATION SYSTEM SHALL BE |
| | NOT LESS THAN THE NUMBER DETERMINED FROM THE ESTIMATED |
| | MAXIMUM OCCUPANT LOAD RATE INDICATED IN TABLE |
| | 403.3.1.1. |
| | |
| | 2) SHEET M2.1: WHERE IS THE DETAIL SHOWING WHAT KEYNOTE |
| | 1 IS ASKING FOR? IS THIS NEW DUCTWORK IN A SHAFT? FBC |
| | 107.2.1 |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |