| 2023-01-25 11:30:51 | FBC-2020 RES. PLUMBING |
| | PERMIT- 22030683 |
| | 1/25/23 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET A102: 2ND REQUEST TO PROVIDE EMERGENCY ROOF |
| | SCUPPER LOCATIONS AND OPENING DIMENSIONS- SEC. R903.4.1 |
| | FBC RES. |
| | |
| | 2) SHEET P101 & P104: PLEASE REMOVE THE GREASE |
| | INTERCEPTORS EQUIPMENT SCHEDULE AND LOCATION FROM THE |
| | PLANS. THIS PROPOSED PROJECT IS AN ADDITION TO A |
| | SINGLE-FAMILY RESIDENTIAL HOME (SEE SHEET C101) AND |
| | GREASE INTERCEPTORS ARE NOT REQUIRED PER SEC. R101.2 |
| | FBC RES. CODE & SEC. 90-125(7) WPB CODE OF ORDINANCES. |
| | IF THE INTENTION IS TO CHANGE THE OCCUPANCY OF THE HOME |
| | AT A LATER DATE AND INSTALL A GREASE INTERCEPTOR, THEN |
| | BOTH THE CHANGE OF OCCUPANCY AND THE GREASE INTERCEPTOR |
| | SHALL BE DONE UNDER SEPARATE PERMITS AND COMPLETE PLANS |
| | AND SPECIFICATIONS SHALL BE PROVIDED FOR DEVELOPMENT |
| | SERVICE DEPARTMENT REVIEW. PLEASE NOTE THE CURRENT PLAN |
| | SHOWS THE SANITARY SEWER LINE FROM THE DOMESTIC |
| | HOUSEHOLD FIXTURES DRAINING INTO THE GREASE INTERCEPTOR |
| | WHICH IS PROHIBITED PER SEC. 1003.3.1 FBC P. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |