| 2022-10-24 08:40:49 | FBC-2020 RES. PLUMBING |
| | PERMIT- 22030683 |
| | 10/24/22 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET A102 ROOF DRAINAGE- SEC. R903.4 FBC RES. |
| | PLEASE PROVIDE ON THE PLAN: |
| | A) RAINFALL RATE. |
| | B) SQUARE FOOTAGE OF THE ROOF AND PARAPETS. |
| | C) GPM FLOW AT EACH SCUPPER LOCATION. |
| | D) SCUPPER DETAIL INCLUDING OPENING DIMENSIONS. |
| | E) DOWNSPOUT SIZES. |
| | F) EMERGENCY ROOF SCUPPER LOCATIONS AND OPENING |
| | DIMENSIONS. |
| | FOR FURTHER INFORMATION PLEASE REFER TO SECS. 1105 & |
| | 1106 FBC P. |
| | |
| | 2) SHEETS P105 & SITE DRAWING #200: THE RISER DRAWING |
| | ON P105 DOES NOT MATCH THE SITE PLAN SHOWING SEPARATE |
| | BUILDING DRAINS FOR THE EXISTING RESIDENCE AND THE |
| | 3-STORY ADDITION- SEC. 107.2.1 WPB. THE SITE PLAN |
| | SHOULD BE SHOWING TWO-WAY CLEANOUTS AT THE JUNCTIONS OF |
| | THE BUILDING DRAINS AND SEWER LINES AT EACH 3-STORY |
| | HOUSE LOCATION- SEC. P3005.2.3 & P3005.2.8 FBC RES. |
| | |
| | 3) SITE DRAWING #200: PLEASE SHOW A HOSE BIB WITH |
| | VACCUM BREAKER WILL BE INSTALLED AT THE EXTERIOR WATER |
| | FAUCET LOCATION SHOWN ON THE PLAN- SECS. P2902.2 & |
| | P2902.4.3 FBC RES. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |
| 2022-10-22 11:18:17 | COULD NOT VERIFY PLUMBING REVIEWERS STAMP. CT |