| Plan Review Notes For Permit 22030683 |
| Permit Number |
22030683 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2022-06-01 08:42:45 | THE MECHANICAL EQUIPMENT SIZING CALCULATIONS SHOWS 2100 | | | TOTAL SQUARE FOOTAGE FOR THIS BUILDING WITH A COOLING | | | BTUH OF 23,409. THIS IS FOR THE ENTIRE BUILDING BUT | | | M101 INDICATES THAT AC-1 IS A 1.5 TON UNIT AND YOU HAVE | | | ONE OF THESE INSTALLED PER FLOOR. PROVIDE MECHANICAL | | | UNITS THAT WOULD BE SIZED PER FLOOR ACCORDING TO THE | | | MECHANICAL EQUIPMENT SIZING CALCULATIONS. THE | | | MECHANICAL SIZING CALCULATIONS CALL FOR A 2 TON SYSTEM | | | FOR THE ENTIRE ADDITION, WHAT IS SUBMITTED IS A 1.5 TON | | | FOR EACH FLOOR. THIS IS OVER SIZED. | | | | | | FEC R403.7.1.2.1 HEAT PUMPS. HEAT PUMP SIZING SHALL BE | | | BASED ON THE COOLING REQUIREMENTS AS CALCULATED | | | ACCORDING TO SECTION R403.7.1.1, AND THE HEAT PUMP | | | TOTAL COOLING CAPACITY SHALL NOT BE MORE THAN 1.15 | | | TIMES GREATER THAN THE DESIGN COOLING LOAD EVEN IF THE | | | DESIGN HEATING LOAD IS 1.15 TIMES GREATER THAN THE | | | DESIGN COOLING LOAD. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|