Plan Review Notes
Plan Review Notes For Permit 22030683
Permit Number 22030683
Review Stop M
Sequence Number 2
Notes
Date Text
2022-06-01 08:42:45THE MECHANICAL EQUIPMENT SIZING CALCULATIONS SHOWS 2100
 TOTAL SQUARE FOOTAGE FOR THIS BUILDING WITH A COOLING
 BTUH OF 23,409. THIS IS FOR THE ENTIRE BUILDING BUT
 M101 INDICATES THAT AC-1 IS A 1.5 TON UNIT AND YOU HAVE
 ONE OF THESE INSTALLED PER FLOOR. PROVIDE MECHANICAL
 UNITS THAT WOULD BE SIZED PER FLOOR ACCORDING TO THE
 MECHANICAL EQUIPMENT SIZING CALCULATIONS. THE
 MECHANICAL SIZING CALCULATIONS CALL FOR A 2 TON SYSTEM
 FOR THE ENTIRE ADDITION, WHAT IS SUBMITTED IS A 1.5 TON
 FOR EACH FLOOR. THIS IS OVER SIZED.
  
 FEC R403.7.1.2.1 HEAT PUMPS. HEAT PUMP SIZING SHALL BE
 BASED ON THE COOLING REQUIREMENTS AS CALCULATED
 ACCORDING TO SECTION R403.7.1.1, AND THE HEAT PUMP
 TOTAL COOLING CAPACITY SHALL NOT BE MORE THAN 1.15
 TIMES GREATER THAN THE DESIGN COOLING LOAD EVEN IF THE
 DESIGN HEATING LOAD IS 1.15 TIMES GREATER THAN THE
 DESIGN COOLING LOAD.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER