2022-04-02 12:14:10PLAN REVIEW BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 BU1635 BN4338
 ASFPM CFM US-21-11935
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NFPA 70 2017 EDITION NEC 2017
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 NOTICE: VALUE HAS BEEN INCREASED TO $302,799, PER THE
 ICC BUILDING VALUATION DATA.
  
 1. THE SOILS REPORT SUBMITTED FOR REVIEW IS FROM THE
 1-STORY STRUCTURE UNDER PERMIT 21030578.
 PROVIDE A SOILS REPORT FOR THE PROPOSED 3-STORY
 STRUCTURE.
 R401.4 SOIL TESTS.
 WHERE QUANTIFIABLE DATA CREATED BY ACCEPTED SOIL
 SCIENCE METHODOLOGIES INDICATE EXPANSIVE, COMPRESSIBLE,
 SHIFTING OR OTHER QUESTIONABLE SOIL CHARACTERISTICS ARE
 LIKELY TO BE PRESENT, THE BUILDING OFFICIAL SHALL
 DETERMINE WHETHER TO REQUIRE A SOIL TEST TO DETERMINE
 THE SOILS CHARACTERISTICS AT A PARTICULAR LOCATION.
 THIS TEST SHALL BE DONE BY AN APPROVED AGENCY USING AN
 APPROVED METHOD.
  
 2. PROVIDE A SITE DRAINAGE PLAN PER FBC R401.3
 IT SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND
 INCLUDED BOUNDARY LINE SURVEY.
 FBC R401.3 SITE DRAINAGE
 SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER
 CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT
 DOES NOT CREATE A HAZARD.
 LOTS SHALL BE GRADED TO DRAIN SURFACE WATER AWAY FROM
 FOUNDATION WALLS. THE GRADE SHALL FALL A MINIMUM OF 6
 INCHES WITHIN THE FIRST 10 FEET.
 2A) IDENTIFY THE LOCATION OF THE UNDERGROUND DRAIN
 PIPES.
 2B) PROVIDE DETAIL OF TERMINAL DEVICES AT SIDEWALK.
  
 3.PROVIDE ROOF DRAINAGE PLAN. PROVIDE NUMBER AND
 LOCATION OF DRAINS AND SCUPPERS BASED ON THE ROOF AREA
 TO BE DRAINED.
 R903.4ROOF DRAINAGE.
 UNLESS ROOFS ARE SLOPED TO DRAIN OVER ROOF EDGES, ROOF
 DRAINS SHALL BE INSTALLED AT EACH LOW POINT OF THE
 ROOF. WHERE REQUIRED FOR ROOF DRAINAGE, SCUPPERS SHALL
 BE PLACED LEVEL WITH THE ROOF SURFACE IN A WALL OR
 PARAPET. THE SCUPPER SHALL BE LOCATED AS DETERMINED BY
 THE ROOF SLOPE AND CONTRIBUTING ROOF AREA.
 R903.4.1OVERFLOW DRAINS AND SCUPPERS.
 WHEN OTHER MEANS OF DRAINAGE OF OVERFLOW WATER IS NOT
 PROVIDED, OVERFLOW SCUPPERS SHALL BE PLACED IN WALLS OR
 PARAPETS NOT LESS THAN 2 INCHES (51 MM) NOR MORE THAN 4
 INCHES (102 MM) ABOVE THE FINISHED ROOF COVERING AND
 SHALL BE LOCATED AS CLOSE AS PRACTICAL TO REQUIRED
 VERTICAL LEADERS OR DOWN-SPOUTS OR WALL AND PARAPET
 SCUPPERS. AN OVERFLOW SCUPPER SHALL BE SIZED IN
 ACCORDANCE WITH THE FLORIDA BUILDING CODE, PLUMBING.
 OVERFLOW DRAINS SHALL DISCHARGE TO AN APPROVED LOCATION
 AND SHALL NOT BE CONNECTED TO ROOF DRAIN LINES.
  
 4.GUTTERS
 R903.4.2ONE AND TWO-FAMILY DWELLINGS, AND PRIVATE
 GARAGES.
 WHEN GUTTERS AND LEADERS ARE PLACED ON THE OUTSIDE OF
 BUILDINGS, THE GUTTERS AND LEADERS SHALL BE CONSTRUCTED
 OF METAL OR APPROVED PLASTIC FOR OUTDOOR EXPOSURE WITH
 LAPPED, SOLDERED OR CAULKED JOINTS AND SHALL BE
 SECURELY FASTENED TO THE BUILDING WITH A CORROSION
 RESISTANT FASTENING DEVICE OF SIMILAR OR COMPATIBLE
 MATERIAL TO THE GUTTERS AND DOWNSPOUTS.
  
 5. THE HIGH ROOF FRAMING PLAN APPEARS TO BE A COPY OF
 THE 2ND AND 3RD FLOOR FRAMING PLANS.
 IDENTIFY ROOFTOP ACCESS.
 PROVIDE PRODUCT APPROVAL OR UL REPORT FOR ACCESS HATCH.
 (BILCO)
 PROVIDE DETAIL OF GUARDRAIL ATTACHMENT.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 6. PRODUCT APPROVAL FL251-R32 HAS EXPIRED.
 PROVIDE A COPY OF THE CURRENT FLORIDA PRODUCT APPROVAL
 OR MIAMI-DADE NOA, APPROVED UNDER THE 2020 FBC, FOR THE
 PROPOSED EXT. FIBERGLASS DOOR.
 FL PRODUCT APPROVALS SHALL INCLUDE THE COVER SHEETS,
 EVALUATION REPORT AND INSTALLATIONS INSTRUCTIONS.
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 7. ONLY THE EVALUATION REPORT WAS SUBMITTED FOR REVIEW
 FOR THE EXTERIOR SWINGING DOOR.
 PROVIDE THE FL PRODUCT APPROVAL COVER SHEETS FOR THE
 PROPOSED EXT. DOOR.
 THE COVER SHEET PROVIDES THE APPROVAL NUMBER, CODE
 VERSION, AND STATUS, FBC R 301.
 FL PRODUCT APPROVALS SHALL INCLUDE THE COVER SHEETS,
 EVALUATION REPORT AND INSTALLATIONS INSTRUCTIONS.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 8. PROVIDE PRODUCT APPROVALS FOR THE PROPOSED WINDOWS.
 PROVIDE A COPY OF THE CURRENT FLORIDA PRODUCT APPROVAL
 OR MIAMI-DADE NOA, APPROVED UNDER THE 2020 FBC, FOR THE
 PROPOSED EXT. FIBERGLASS DOOR.
 FL PRODUCT APPROVALS SHALL INCLUDE THE COVER SHEETS,
 EVALUATION REPORT AND INSTALLATIONS INSTRUCTIONS.
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 9. IDENTIFY CEILING AND WALL INSULATION TYPE AND R
 VALUE ON PLANS.
 R402.1 GENERAL (PRESCRIPTIVE).
 THE BUILDING THERMAL ENVELOPE SHALL MEET THE
 REQUIREMENTS OF SECTIONS R402.1.1 THROUGH R402.1.4.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
  
  
  
  
  
  
  