| Plan Review Notes For Permit 22030682 |
| Permit Number |
22030682 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2022-04-08 15:25:08 | PETER E VALENTI | | | BUILDING PLANS EXAMINER II | | | [email protected] | | | 561 805 6673 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC M = FBC MECHANICAL | | | FBC FG = FBC FUEL GAS | | | | | | BUILDING REVIEW DENIED: | | | | | | FBC B 107.2.1, THE TEST RESULTS THAT WERE SUBMITTED ARE | | | FOR A 6" THICK SLAB WITH A DROPPED CEILING. THE PROBLEM | | | WITH THAT SUBMITTAL IS THAT THERE IS NO DROP | | | /DRYWALL CEILING EXCEPT IN MINIMAL AREAS OF THE KITCHEN | | | AND POSSIBLY BATHROOM. | | | PLEASE PROVIDE THE TEST RESULTS FOR 6" SLAB WITH NO | | | DROP CEILING. |
|