| 2022-03-30 09:06:56 | PETER E VALENTI | | | BUILDING PLANS EXAMINER II | | | [email protected] | | | 561 805 6673 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC M = FBC MECHANICAL | | | FBC FG = FBC FUEL GAS | | | | | | BUILDING REVIEW DENIED: | | | | | | PLEASE PROVIDE THE FOLLOWING INFORMATION: | | | | | | DESCRIPTION OF EXISTING SITE CONDITIONS: | | | THICKNESS OF SLAB | | | PROPOSED UNDERLAYMENT. | | | TEST REPORTS FOR THE PROPOSED UNDERLAYMENT BASED ON THE | | | EXISTING SITE CONDITIONS. | | | TEST REPORTS MAY BE BASED ON THE FOLLOWING ASTM'S: | | | E-84, E-90 & E-492. | | | | | | | | | FBC 603.1 FLAME SPREAD - ASTM E 84-09 | | | | | | FBC 1207.2 AIR-BORNE SOUND. ASTM E 90-04 | | | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES | | | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM | | | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION | | | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) | | | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM | | | E 90. | | | | | | FBC 1207.3 STRUCTURE-BORNE SOUND. ASTM E 492-09 | | | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR | | | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA | | | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION | | | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD | | | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. | | | | | | | | | | | | | | | | | | | | | |
|