| Plan Review Notes For Permit 22030664 |
| Permit Number |
22030664 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2022-07-18 15:42:51 | PETER E VALENTI | | | BUILDING PLANS EXAMINER II | | | [email protected] | | | 561 805 6673 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC M = FBC MECHANICAL | | | FBC FG = FBC FUEL GAS | | | | | | BUILDING REVIEW FAILED: | | | | | | 4.) ROOFING UNDERLAYMENT MUST COMPLY WITH FBC R | | | 905.1.1.1. (DOUBLE UNDERLAYMENT OR OTHER APPROVED | | | METHOD). PLEASE SHOW METHOD OF COMPLIANCE ON PLAN. | | | 5.) FBC R 311.7.8.1, THE HANDRAILS CAN BE NO HIGHER | | | THAN 38" MEASURED VERTICALLY FROM THE SLOPED PLAIN | | | ADJOINING THE TREAD NOSING. PLEASE CORRECT THE HEIGHT | | | ON PLAN DETAILS. | | | |
|