2022-06-23 10:07:232ND PLUMBING REVIEW
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2020 FRC P3108.2.1 - THE POOL BATH HAS TWO TRAPS
 UPSTREAM OF THE VENTED FIXTURE CONNECTION AND ONLY ONE
 IS ALLOWED. THE LAVATOR WOULD NEED TO CONNECT BETWEEN
 THE WATER CLOSET AND THE SHOWER TO BE IN COMPLIANCE.
  
 NOTE: I'VE ADDED A GAS REVIEW TO THIS PERMIT AS YOU
 HAVE ADDED GAS TO THE DRAWING. YOU WILL NEED TO PULL A
 GAS SUB-PERMIT OR A SEPARATE PERMIT FOR THE GAS.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  