| 2022-06-23 10:07:23 | 2ND PLUMBING REVIEW | | | | | | V7 FPC - 2020 FLORIDA PLUMBING CODE | | | V7 FGC - 2020 FLORIDA FUEL GAS | | | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE | | | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE | | | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE | | | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION | | | 2021 F.S. - 2021 FLORIDA STATUTES | | | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE | | | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE | | | FBC CHAPTER 1 | | | | | | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED | | | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. | | | | | | 1. 2020 FRC P3108.2.1 - THE POOL BATH HAS TWO TRAPS | | | UPSTREAM OF THE VENTED FIXTURE CONNECTION AND ONLY ONE | | | IS ALLOWED. THE LAVATOR WOULD NEED TO CONNECT BETWEEN | | | THE WATER CLOSET AND THE SHOWER TO BE IN COMPLIANCE. | | | | | | NOTE: I'VE ADDED A GAS REVIEW TO THIS PERMIT AS YOU | | | HAVE ADDED GAS TO THE DRAWING. YOU WILL NEED TO PULL A | | | GAS SUB-PERMIT OR A SEPARATE PERMIT FOR THE GAS. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | | | | RYAN W. BROWN | | | CHIEF PLUMBING INSPECTOR | | | OFFICE: 561-805-6692 | | | CELL: 561-517-4293 | | | EMAIL: [email protected] | | | |
|