Plan Review Notes
Plan Review Notes For Permit 22030664
Permit Number 22030664
Review Stop P
Sequence Number 1
Notes
Date Text
2022-03-23 10:36:0203/23/22 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. ON SHEET P-2, THE TOILET IN THE MASTER DOES NOT HAVE
 A HORIZONTAL WET VENT, AND IT IS A DRY VENT PER THE
 2020 R 3104.3 VENT CONNECTION TO THE DRAINAGE SYSTEM.
 WHEN CORRECTING, IT MUST BE DOWNSTREAM OF BATHROOM
 GROUPS OF THE WET VENT PER THE 2020 FBC SEC.
 3108.1HORIZONTAL WET VENT PERMITTED.
  
 2. ON THAT SAME SHEET, THE LAV IS NOT SHOWN FOR THE
 POOL CABANA. WOULD YOU PLEASE CORRECT PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
 THE LAUNDRY SINK CANNOT DISCHARGE INTO THE WET VET OF A
 BATHROOM GROUP; IT MUST BE DOWNSTREAM PER THE 2020 FBC
 SECTION R3108.1 HORIZONTAL WET VENT PERMITTED.
  
 3. ON SHEET, E-1 SHOWS FOUR TANK-LESS, BUT IT HAS ONLY
 TWO ON THE ISOMETRIC. WOULD YOU PLEASE CORRECT PER THE
 WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 WEST PALM BEACH AMENDMENTS 2017 FBC CHAPTER; UPON
 REQUEST.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  