| Plan Review Notes For Permit 22030664 |
| Permit Number |
22030664 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-06-03 15:31:13 | PETER E VALENTI | | | BUILDING PLANS EXAMINER II | | | [email protected] | | | 561 805 6673 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC M = FBC MECHANICAL | | | FBC FG = FBC FUEL GAS | | | | | | BUILDING REVIEW DENIED: | | | | | | 1.) FBC B 107.2.1, PLAN SHEET A-1 (EAST SIDE) INDICATES | | | A MEASUREMENT OF 38.28'. THIS APPEARS TO BE INCORRECT. | | | 2.) FBC B 107.2.1, PLAN SHEET A-1 (DESIGN CRITERIA) | | | INDICATES THE HIGHEST MEAN HEIGHT OF 15'. THIS APPEARS | | | TO BE INCORRECT. | | | 3.) FBC B 107.2.1, PLAN SHEET S-1 DETAILED SECTIONS | | | (H/S.1 & I/S.1) DO NOT MATCH THE INDICATIONS ON FLOOR | | | PLAN. THE DETAILS APPEAR TO BE MIXED UP. | | | 4.) FBC B 107.2.1, PROVIDE THE PRODUCT APPROVALS FOR | | | ROOFING MATERIAL, WINDOWS, AND DOORS. | | | 5.) FBC B 107.2.1, PROVIDE ALL STAIR CONNECTION | | | DETAILS. | | | 6.) FBC R 312.1 & FBC B 1607.8.1.1, PROVIDE THE BALCONY | | | HAND RAIL CONNECTION DETAILS. | | | 7.) FBC R 402, PROVIDE THE ENERGY CALCULATIONS. | | | |
|