| 2022-10-04 17:09:15 | 1ST REVIEW FMC |
| | PERMIT: 22030607 |
| | |
| | CODES IN EFFECT: 2020 |
| | |
| | |
| | FBC- FLORIDA BUILDING CODE |
| | FMC- FLORIDA MECHANICAL CODE |
| | FEC- FLORIDA ENERGY CONSERVATION |
| | |
| | FGC- FLORIDA FUEL GAS |
| | FEX- FLORIDA EXISTING BUILDING CODE |
| | FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| | F.S.- FLORIDA STATUTES |
| | FAC- FLORIDA ACCESSIBILITY CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE CALCULATIONS SUBMITTED ON 3/16/2022 AND AGAIN ON |
| | 9/23/2022 ARE THE MECHANICAL EQUIPMENT SIZING |
| | CALCULATIONS. I DO NOT NEED THEM AGAIN. PLEASE SUBMIT |
| | THE ENERGY CALCULATIONS THAT I HAVE ASKED FOR IN BOTH |
| | REVIEW CYCLES. FEC 402 |
| | |
| | 2) PLEASE ADDRESS PREVIOUS COMMENT 2; SHOW THE |
| | ANCHORING DETAIL OF THE CONDENSING UNITS. FRC M1307.2 |
| | |
| | 3) THE MAKE-UP AIR FOR THE KITCHEN HOOD SHOULD BE |
| | BROUGHT IN FROM THE OUTDOORS WITH A DAMPER THAT WILL |
| | REMAIN CLOSED UNTIL THE HOOD FAN IS ACTIVATED. FRC |
| | M1503.4 |
| | |
| | 4) THE NEW LAUNDRY ROOM INDICATES THERE ARE 2 STACKED |
| | WASHERS AND DRYERS. PLEASE SHOW BOTH DRYER DUCTS. FRC |
| | M1502.3 |
| | |
| | 5) PLEASE PROVIDE THE DUCT SIZES FOR ALL DUCT WORK |
| | SIZES FOR THE NEW DUCTWORK, INCLUDING THE FLEX DUCT AND |
| | RETURNS. FBC 107.3.5 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |