| 2022-04-05 17:26:19 | 1ST REVIEW FBC-2020 MECHANICAL |
| | PERMIT-22030607 |
| | |
| | CODES IN EFFECT: 2020 |
| | |
| | FBC- FLORIDA BUILDING CODE |
| | FMC- FLORIDA MECHANICAL CODE |
| | FEC- FLORIDA ENERGY CONSERVATION |
| | FGC- FLORIDA FUEL GAS |
| | FEX- FLORIDA EXISTING BUILDING CODE |
| | FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| | F.S.- FLORIDA STATUTES |
| | FAC- FLORIDA ACCESSIBILITY CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE PROVIDE THE ENERGY CALCULATIONS FOR THE NEW |
| | ADDITION, SPACES THAT WERE CONVERTED TO CONDITIONED |
| | SPACE INCLUDING THE GARAGE. THIS SHOULD SHOW THE GARAGE |
| | DOOR. FEC R402 |
| | |
| | 2) PLEASE SHOW THE ANCHORING OF THE CONDENSING UNITS. |
| | FRC M1307.2 |
| | |
| | 3) PLEASE SHOW THE CONDENSATE DRAIN LINES AND THE |
| | TERMINATION LOCATION. FRC 307 |
| | |
| | 4) PLEASE SHOW THE BATHROOM EXHAUST FANS AND THE |
| | EXHAUST TERMINATION LOCATION. FRC 303.3 |
| | |
| | 5) PLEASE PROVIDE SPECIFICATIONS FOR THE HOOD EXHAUST |
| | FAN TO SHOW IT COMPLIES WITH THE MAKE-UP AIR |
| | REQUIREMENTS OF FRC M1503.4 |
| | |
| | 6) PLEASE SHOW THE DRYER EXHAUST AND TERMINATION |
| | LOCATION. FRC M1502.3 |
| | |
| | 7) PLEASE PROVIDE DUCT SIZES AND CFM?S OF AIR FOR THE |
| | NEW DUCT WORK AND GRILLES. FBC 107.2.1 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |