| Date |
Text |
| 2022-04-13 10:47:36 | ELECTRICAL REVIEW FAILED |
| | 1) PLEASE DETAIL INTERIOR LOCATIONS FOR ELECTRIC PANELS |
| | . FBC 107.2 |
| | 2) PLEASE PROVIDE SITE PLAN DETAILING ALL OUTSIDE |
| | DISCONNECTS AND METERS. FBC 107.2 |
| | 3) RISER DIAGRAM DETAILS (3) ELECTRIC PANELS. THE PANEL |
| | FEEDERS APPEAR TO BE SIZED USING NEC 310.15 (B)(7)(2). |
| | THESE FEEDERS TO NOT SUPPLY THE ENTIRE LOAD AS OUTLINED |
| | BY THIS SECTION. THIS SECTION IS NOT APPLICABLE TO SIZE |
| | THESE FEEDERS. PLEASE CORRECT AND SIZE FEEDERS AS PER |
| | 310.15 TABLES |
| | 4) PLEASE INCLUDE A NOTE WITH DRAWINGS STATING |
| | GENERATORS, POOL AND SITE LIGHTING ARE UNDER SEPARATE |
| | PERMITS |
| | 5) PLEASE DETAIL ALL OUTDOOR RECEPTACLES AS PER NEC |
| | 210.50 (E), 210.63 AND 210.64 |
| | 6) PLEASE DETAIL ALL RECEPTACLES REQUIRED AS PER 250.50 |
| | (D) |
| | 7) PLEASE DETAIL ARC FAULT PROTECTION COMPLIANCE WITH |
| | NEC 210.12 |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. |
| | |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2020 7TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| | 7TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | MICHAEL PETERSON |
| | ELECTRICAL PLANS EXAMINER |
| | [email protected] |
| | 561-805-6746 |
| | |
| | |