| Date |
Text |
| 2022-06-16 16:01:45 | PETER E VALENTI |
| | BUILDING PLANS EXAMINER II |
| | [email protected] |
| | 561 805 6673 |
| | |
| | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| | FBC B = FBC BUILDING |
| | FBC R = FBC RESIDENTIAL |
| | FBC EB = EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | FBC M = FBC MECHANICAL |
| | FBC FG = FBC FUEL GAS |
| | |
| | BUILDING REVIEW DENIED: |
| | |
| | 1.) FBC B 107.2.1, COMPLETE THE DEMO DEBRIS FORM: HTTP: |
| | //WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/BUILDI |
| | NG-PERMIT-FORMS |
| | IF THE FORM IS NOT AVAILABLE ONLINE, PLEASE REQUEST FOR |
| | THE FORM. |
| | 2.) FBC B 107.2, PROVIDE INFORMATION AS TO HOW THE |
| | JOB-SITE RUN-OFF WATER/DEBRIS WILL BE PREVENTED SUCH AS |
| | SILT FENCES AND STORM INLET FILTERING. |
| | 3.) FBC B 107.2.1, PROVIDE A SEPARATE DRIVEWAY PERMIT. |
| | 4.) FBC B 107.2.1, PROVIDE CLARITY AS TO WHICH AREAS OF |
| | ATTIC/UNDERSIDE OF ROOF ARE TO RECEIVE BATT INSULATION |
| | AND WHICH AREAS ARE TO RECEIVE ICENYNE FOAM SPRAY |
| | INSULATION. PLAN SHEETS A7.1 & A7.2 INDICATE SPRAY FOAM |
| | INSULATION BUT PLAN SHEET S10.3 INDICATES BATT |
| | INSULATION. |
| | 5.) FBC B 107.2.1, PROVIDE THE STRUCURAL DETAILS FOR |
| | NEW PARAPET WALLS. |
| | 6.) FBC B 107.2.1, INDICATE ON PLANS WHICH WALLS & |
| | COLUMNS ARE LOAD BEARING AND INDICATE SHORING. |
| | 7.) FBC B 107.2.1, PROVIDE DETAILS FOR THE HAND FRAMED |
| | WOOD BEAMS AND TRELLIS WORK INCLUDING FASTENERS AND |
| | CONNECTORS TO BE USED. |
| | 8.) FBC B 107.2.1, PLAN SHEET A0.1 IS MISSING. A |
| | DRAINAGE PLAN IS REQUIRED. |
| | 9.) FBC B 107.2.1, PLAN SHEET A0.0 APPEARS TO BE THE |
| | INDEX SHEET. THIS INDEX DOES NOT INCLUDE ALL PLAN |
| | SHEETS: A2.1, A2.2 & A3.3 ARE NOT ON THE INDEX. |
| | 10.) FBC B 107.2.1, SEVERAL OF THE PLAN SHEETS HAVE |
| | BEEN IDENTIFIED ON THE INDEX AS ARCHITECTURALS BUT ON |
| | THE PLAN SHEETS THEY HAVE DIFFERENT SHEET NUMBERS |
| | SPECIFIC TO STRUCTURAL, MECHANICAL, ELECTRICAL, & |
| | PLUMBING. PLEASE CORRECT THIS SO THEY MATCH. |
| | 11.) FBC B 107.2.1, PLAN SHEET A0.0 (COVER SHEET) |
| | INDICATES THE COVERED AREA OF THE EXISTING HOUSE IS 427 |
| | S.F., PLEASE CLARIFY THE AREA THIS REFERS TO. |
| | 12.) FBC B 310, PLAN SHEET A0.0 OCCUPANCY SECTION IS |
| | INCOMPLETE. PLEASE INCLUDE THE TYPE OF RESIDENTIAL |
| | OCCUPANCY, SUCH AS R-3. |
| | 13. FBC B R 806.5, PROVIDE INFORMATION FOR A NON-VENTED |
| | ATTIC SPACE AND SHOW WHICH OPTIONS, FROM THE CODE, ARE |
| | TO BE USED AS ICENYNE FOAM SPRAY IS INDICATED ON PLAN |
| | SHEET A7.1 & A7.2. |
| | 14.) FBC B 107.2.1, FBC B 107.3.4.1, PLEASE SUBMIT ALL |
| | PRODUCT APPROVALS/MANUFACTURER'S SPECIFICATIONS |
| | INCLUDING ROOFING MATERIAL, ICENYNE, TRELLIS CANVAS, |
| | GLUE LAMINATE BEAMS, & GARAGE DOOR. IF THESE ITEMS ARE |
| | TO BE DEFERRED, PLEASE LIST THEM ON PLAN SHEET. |
| | 15.) FBC EC R101.5, PLEASE PROVIDE THE COMPLETED ENERGY |
| | CALCULATIONS PER THE ENERGY CONSERVATION CODE. |
| | 16.) FBC B 107.2.1, PROVIDE FLAT ROOF DETAILS FOR FLAT |
| | ROOF. |
| | |