| Plan Review Notes For Permit 22030597 |
| Permit Number |
22030597 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-04-27 15:40:19 | ADD OVERHEAD DOOR - | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) PLEASE PROVIDE A FLOOR PLAN SHOWING THE LOCATION OF | | | THE NEW DOOR. | | | | | | 2) PLEASE SHOW THE TIEBEAM OR LINTEL FOR THE MASONRY | | | ABOVE THE NEW DOOR OPENING - FBC 1403.3 STRUCTURAL. | | | EXTERIOR WALLS, AND THE ASSOCIATED OPENINGS, SHALL BE | | | DESIGNED AND CONSTRUCTED TO RESIST SAFELY THE | | | SUPERIMPOSED LOADS REQUIRED BY CHAPTER 16. - FBC 1609.1 | | | APPLICATIONS. | | | BUILDINGS, STRUCTURES AND PARTS THEREOF SHALL BE | | | DESIGNED TO WITHSTAND THE MINIMUM WIND LOADS PRESCRIBED | | | HEREIN. DECREASES IN WIND LOADS SHALL NOT BE MADE FOR | | | THE EFFECT OF SHIELDING BY OTHER STRUCTURES. ALL | | | EXTERIOR WALL COVERINGS AND SOFFITS SHALL BE CAPABLE OF | | | RESISTING THE DESIGN PRESSURES SPECIFIED FOR WALLS FOR | | | COMPONENTS AND CLADDING LOADS IN ACCORDANCE WITH | | | SECTION 1609.1.1. | | | |
|