Plan Review Notes
Plan Review Notes For Permit 22030591
Permit Number 22030591
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2022-06-16 11:58:59FIRE COMMENT:
  
 PER NFPA 90A
  
 6.4 SMOKE DETECTION FOR AUTOMATIC CONTROL
  
 6.4.2 LOCATION
  
 6.4.2.1 SMOKE DETECTORS LISTED FOR USE IN AIR
 DISTRIBUTION SYSTEMS SHALL BE LOCATED AS FOLLOWS:
  
 (1) DOWNSTREAM OF THE AIR FILTERS AND AHEAD OF ANY
 BRANCH CONNECTIONS IN AIR SUPPLY SYSTEMS HAVING A
 CAPACITY OF GREATER THAT 944 L/SEC(2000FT3/MIN.)
 (2) AT EACH STORY PRIOR TO THE CONNECTION TO A COMMON
 RETURN AND PRIOR TO ANY RECIRCULATION OF FRESH AIR
 INLET CONNECTION IN AIR RETURN SYSTEMS HAVE A CAPACITY
 GREATER THAN 7080L/SEC(15.000FT3/MIN) AND SERVING MORE
 THAN ONE STORY.
  
 6.4.3* FUNCTION.
 6.4.3.1 SMOKE DETECTORS PROVIDED AS REQUIRED BY 6.4.2
 SHALL AUTOMATICALLY STOP THEIR RESPECTIVE FAN(S) ON
 DETECTING THE PRESENCE OF SMOKE.
  
 6.4.4 INSTALLATION
  
 6.4.4.1 SMOKE DETECTORS SHALL BE INSTALLED, TESTED, AND
 MAINTAINED IN ACCORDANCE WITH NFPA 72.
  
 6.4.4.2.1 SMOKE DETECTORS USED SOLELY FOR CLOSING
 DAMPERS OR FOR HEATING, VENTILATING, AND
 AIR-CONDITIONING SYSTEM SHUTDOWN SHALL NOT BE REQUIRED
 TO ACTIVATE THE BUILDING EVACUATION ALARM.
  
 PER NFPA 72, 2016 ED
  
 CHAPTER 21 EMERGENCY CONTROL FUNCTION INTERFACES
 21.7 HEATING, VENTILATING AND AIR-CONDITIONING (HVAC)
 SYSTEMS.
 21.7.1 THE PROVISIONS OF SECTION SHALL APPLY TO THE
 BASIC METHOD BY WHICH A FIRE ALARM SYSTEM INTERFACES
 WITH THE HEATING, VENTILATING, AND AIR-CONDITIONING
 (HVAC) SYSTEM
 21.7.4 SMOKE DETECTORS MOUNTED IN THE AIR DUCTS OF HVAC
 SYSTEMS SHALL INITIATE A SUPERVISORY SIGNAL
  