| Plan Review Notes For Permit 22030589 |
| Permit Number |
22030589 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-03-15 12:53:04 | FIRE COMMENTS: | | | (1) CONFLICT OF CARD READER DEVICE LOCATION ON THE TWO | | | PLAN SHEETS SUBMITTED. | | | (2) THE SUBMITTED PLAN DOES NOT INCLUDE MOUNTING HEIGHT | | | AND LOCATION OF THE MANUAL RELEASE DEVICE FROM THE | | | EGRESS SIDE. | | | (3) THE SUBMITTED PLAN DOES NOT INDICATE THE SEQUENCE | | | OF OPERATION UNDER POWER LOSS AND/OR FIRE ALARM | | | OPERATION. | | | REFERENCE NFPA 101, LIFE SAFETY CODE, 7.2.1.6.2 | | | FIRE REVIEW PERFORMED BY: | | | CHARLES ?RANDY? WALKER, SENIOR FIRE INSPECTOR | | | (561) 804-4762 | | | |
|