Plan Review Notes
Plan Review Notes For Permit 22030585
Permit Number 22030585
Review Stop P
Sequence Number 1
Notes
Date Text
2022-03-24 17:48:481ST REVIEW FBC-2020 PLUMBING
 PERMIT- 22030585
 3/24/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS P-3.1, P-4.1, P-4.2: THE THERMOSTAT CONTROLS
 FOR THE WATER HEATERS SHALL NOT SERVE AS THE
 TEMPERATURE LIMITING MEANS FOR MAXIMUM ALLOWABLE HOT
 WATER DELIVERY TEMPERATURE AT THE SINKS AND DISHWASHER-
 SEC. 607.1.1 FBC P. PROVIDE MIXING VALVES.
  
 2) P-4.1: PROVIDE FULL OPEN SHUTOFF VALVES FOR THE COLD
 WATER SUPPLY LINES TO THE WATER HEATERS- SEC. 606.1(8)
 FBC P.
  
 3) P-4.1: PROVIDE AN EQUIPMENT SCHEDULE FOR THE
 DISHWASHER- SEC. 409.1 FBC P.
  
 4) P-1.1, P-3.1: WASTE RECEPTORS MAY BE REQUIRED TO
 CONVEY THE DRAINAGE FROM THE ICE MAKER AND SODA/WATER
 DISPENSERS TO THE SANITARY SYSTEM- SEC. 802.4 FBC P.
 PLEASE PROVIDE PRODUCT SUBMITTALS- SEC. 107.2.1 WPB.
  
 5) PROVIDE THE FOLLOWING DETAILS IN ACCORDANCE WITH THE
 FBC ACCESSIBILITY CODE.
  
 A) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE
 SINKS- SEC. 606.2, 804.4.
  
 B) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE
 DISHWASHER, ICE MACHINE, AND DISPENSER- SEC. 804.6.1,
 804.6.3.
  
 C) REACH HEIGHTS TO APPLIANCE AND BEVERAGE DISPENSER
 CONTROLS- SEC. 308.1.
  
 D) SHOW OPERABLE CONTROL COMPLIANCE FOR APPLIANCES AND
 DISPENSER- SEC. 804.6.2.
  
 E) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 REFRIGERATOR/FREEZER- SEC. 804.6.6.
 COMBINATION REFRIGERATORS AND FREEZERS SHALL HAVE AT
 LEAST 50 PERCENT OF THE FREEZER SPACE 54 INCHES MAXIMUM
 ABOVE THE FINISH FLOOR OR GROUND. THE CLEAR FLOOR OR
 GROUND SPACE SHALL BE POSITIONED FOR A PARALLEL
 APPROACH TO THE SPACE DEDICATED TO A
 REFRIGERATOR/FREEZER WITH THE CENTERLINE OF THE CLEAR
 FLOOR OR GROUND SPACE OFFSET 24 INCHES MAXIMUM FROM THE
 CENTERLINE OF THE DEDICATED SPACE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  