| 2022-03-24 17:48:48 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT- 22030585 |
| | 3/24/2022 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEETS P-3.1, P-4.1, P-4.2: THE THERMOSTAT CONTROLS |
| | FOR THE WATER HEATERS SHALL NOT SERVE AS THE |
| | TEMPERATURE LIMITING MEANS FOR MAXIMUM ALLOWABLE HOT |
| | WATER DELIVERY TEMPERATURE AT THE SINKS AND DISHWASHER- |
| | SEC. 607.1.1 FBC P. PROVIDE MIXING VALVES. |
| | |
| | 2) P-4.1: PROVIDE FULL OPEN SHUTOFF VALVES FOR THE COLD |
| | WATER SUPPLY LINES TO THE WATER HEATERS- SEC. 606.1(8) |
| | FBC P. |
| | |
| | 3) P-4.1: PROVIDE AN EQUIPMENT SCHEDULE FOR THE |
| | DISHWASHER- SEC. 409.1 FBC P. |
| | |
| | 4) P-1.1, P-3.1: WASTE RECEPTORS MAY BE REQUIRED TO |
| | CONVEY THE DRAINAGE FROM THE ICE MAKER AND SODA/WATER |
| | DISPENSERS TO THE SANITARY SYSTEM- SEC. 802.4 FBC P. |
| | PLEASE PROVIDE PRODUCT SUBMITTALS- SEC. 107.2.1 WPB. |
| | |
| | 5) PROVIDE THE FOLLOWING DETAILS IN ACCORDANCE WITH THE |
| | FBC ACCESSIBILITY CODE. |
| | |
| | A) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE |
| | SINKS- SEC. 606.2, 804.4. |
| | |
| | B) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE |
| | DISHWASHER, ICE MACHINE, AND DISPENSER- SEC. 804.6.1, |
| | 804.6.3. |
| | |
| | C) REACH HEIGHTS TO APPLIANCE AND BEVERAGE DISPENSER |
| | CONTROLS- SEC. 308.1. |
| | |
| | D) SHOW OPERABLE CONTROL COMPLIANCE FOR APPLIANCES AND |
| | DISPENSER- SEC. 804.6.2. |
| | |
| | E) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE |
| | REFRIGERATOR/FREEZER- SEC. 804.6.6. |
| | COMBINATION REFRIGERATORS AND FREEZERS SHALL HAVE AT |
| | LEAST 50 PERCENT OF THE FREEZER SPACE 54 INCHES MAXIMUM |
| | ABOVE THE FINISH FLOOR OR GROUND. THE CLEAR FLOOR OR |
| | GROUND SPACE SHALL BE POSITIONED FOR A PARALLEL |
| | APPROACH TO THE SPACE DEDICATED TO A |
| | REFRIGERATOR/FREEZER WITH THE CENTERLINE OF THE CLEAR |
| | FLOOR OR GROUND SPACE OFFSET 24 INCHES MAXIMUM FROM THE |
| | CENTERLINE OF THE DEDICATED SPACE. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |