| 2022-04-01 06:42:24 | 1ST REVIEW FBC-2020 MECHANICAL | | | PERMIT-22030585 | | | | | | CODES IN EFFECT: | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PLEASE PROVIDE OUTDOOR AIR CALCULATIONS FOR EACH USE | | | OF SPACE IN THIS PROJECT. THERE IS A RECEPTION AREA, | | | TEAM ROOMS WHICH APPEAR TO BE NO DIFFERENT THAN THE | | | CONFERENCE ROOMS, CONFERENCE ROOMS, LOUNGE AREA, | | | OFFICES, BREAK ROOM, COPY/PRINT ROOM, STORAGE ROOM. | | | EACH SHOULD HAVE A CALCULATION BASED ON FMC 403.3.1.1 | | | AND TABLE 403.3.1.1. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|