Plan Review Notes
Plan Review Notes For Permit 22030579
Permit Number 22030579
Review Stop M
Sequence Number 3
Notes
Date Text
2022-11-04 10:03:502ND REVIEW FMC
 PERMIT: 22030579
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET A-8: NOTE 1 APPEARS TO BE MISSING FROM THE
 KEYNOTES. PROVIDE A PLAN THAT INCLUDES THIS NOTE. FBC
 107.3.5
  
 2) PROVIDE THE MECHANICAL EQUIPMENT SIZING CALCULATIONS
 FOR THIS PROJECT. FEC R403.7.1
  
 3) PROVIDE THE NEW BATH EXHAUST FAN CFM???S AND SHOW
 THE BATH EXHAUST FAN ON THE DRAWING ALONG WITH THE
 TERMINATION LOCATION. FRC R303.3
  
 4) SHOW THE RETURN AIR PATH FROM ALL ROOMS WITH DOORS
 BACK TO THE AHU. FRC M1602.3
  
 5) IT APPEARS THE NEW AHU IS LOCATED IN THE MIDDLE OF
 THE FLOOR IN THE GARAGE, IS THIS STILL TO BE A CAR
 GARAGE? WILL THE AHU BE PROTECTED?
  
 6) THERE AE DUCTS AND DIFFUSERS THAT APPEAR TO BE
 INSTALLED IN WALLS, PLEASE SHOW THESE IN THE ROOMS THAT
 THEY ARE MEANT TO BE INSTALLED.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  