2022-09-01 09:31:372ND PLUMBING REVIEW
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2017 WPB AMEND 107.3.5.3 (12) - YOUR DIAGRAM FOR THE
 DWV IS NOT IN ISOMETRIC FORM. PLEASE RECONFIGURE THE
 DRAWING TO BE IN A TYPICAL ISOMETRIC CONFIGURATION. THE
 ISOMETRIC SHOULD INCLUDE PIPE SIZES WHERE NEEDED. THE
 ISOMETRIC SHOULD INDICATE DIRECTIONAL FLOW.
  
 2. 2020 FRC P3108.1 - THE CONFIGURATION OF THE FIXTURE
 DRAIN CONNECTIONS DO NOT COMPLY WITH THE CODE. TWO
 TRAPS ON THE HIGH SIDE OF THE VENTED FIXTURE CONNECTION
 IS NOT ALLOWED.
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  