Plan Review Notes
Plan Review Notes For Permit 22030579
Permit Number 22030579
Review Stop G
Sequence Number 1
Notes
Date Text
2022-03-15 15:40:0603/15/22 1ST GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. WOULD YOU PLEASE SUBMIT THE ISOMETRIC DRAWING THAT
 CLEARLY SHOWS THE LENGTH OF ALL CUT SECTIONS OF PIPE
 PER 2020 FBC RES. SECS. G2413.4.1, G2413.4.2. INCLUDE
 PIPE LENGTHS, BTU LOADS, AND DISTANCES TO THE
 APPLIANCES THAT WERE USED TO CALCULATE MINIMUM PIPE
 SIZES USING THE SIZING TABLES FROM THE 2020 FGC 402/FBC
 RES G2413. (INCLUDE REFERENCES TO THE TABLE(S) USED)
  
 2. THIS TANKLESS UNIT CALL FOR A 10.5? WATER COLUMN,
 AND THE SERVICE METER DISCHARGES IS A 12" WATER COLUMN
 REQUIRING A REGULATOR FOR THIS UNIT AS PER THE
 MANUFACTURER'S SPECIFICATION. SUBMIT MANUFACTURER'S
 SPECIFICATIONS FOR THE PRESSURE REGULATORS IF
 APPLICABLE. REGULATORS INSTALLED ON THE EXTERIOR OF THE
 BUILDING SHALL BE APPROVED FOR OUTDOOR INSTALLATION PER
 THE 2020 FBC RES. SEC. G2421.1 OR 410.1.
  
 3. SHOW THE DISTANCE FROM THE POINT OF DELIVERY (GAS
 METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER THE 2020 FBC
 FG SEC. 402.4.1 OR 2020 FBC RES. SEC. G2413.4.1.
  
  
 4. WOULD YOU PLEASE PROVIDE WHAT TYPE OF GAS (LP OR
 NATURAL) IS BEING USED PER THE WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 5. INDICATE THE SYSTEM'S DELIVERY PRESSURE (PSI) ON THE
 PLAN PER THE 2020 FBC FG SEC. 402.2 OR 2020 FBC RES.
 SEC. G2413.2.
  
 6. WOULD YOU PLEASE PROVIDE MANUFACTURES SPECIFICATIONS
 FOR GAS TANKLESS, GRILL BBQ, RANGE, FIREPLACE, AND GAS
 LIGHTS EQUIPMENT TO VERIFY COMPLIANCE WITH 2020 FBC
 RES. SEC. G2408.1. GAS APPLIANCES SHALL BE LISTED AND
 LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES/EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION PER THE 2020 FBC RES. SEC. G2413.2 AND
 G2404.3.
  
 7. IF UTILITIES PROVIDE A REGULATOR, NO SPECIFICATIONS
 ARE REQUIRED BUT SUBMIT THE MANUFACTURER'S
 SPECIFICATIONS FOR THE PRESSURE REGULATORS INSTALLED AT
 TANKLESS OR ANY OTHER LOCATION. REGULATORS INSTALLED ON
 THE EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR
 OUTDOOR INSTALLATION PER THE 2020 FBC RES. SEC.
 G2421.1. A REGULATOR IS REQUIRED TO BRING THE SYSTEM
 DOWN TO 10.5 WC ON THE HEART, BUT THE FPU REGULATOR MAY
 STEP DOWN FOR THIS SYSTEM.
  
 8. WOULD YOU PLEASE SHOW ON THE HOUSE PLAN THE LOCATION
 OF THE TANK-LESS WATER HEATER AND THE LOCATION AND
 DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN RELATION
 TO THE WATER HEATER? THE LOCATION OF THE WATER HEATER
 SHALL COMPLY WITH THE MANUFACTURER'S INSTALLATION
 INSTRUCTIONS. THE HOUSE PLAN CAN BE HAND-DRAWN PER THE
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1. INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 9. HOT WATER LINES NOT IN CONDITION SPACE NEED TO BE
 INSULATED WITH A MINIMUM R-3 PER THE 2020 FBC SEC. RE
 403.5.3. WOULD YOU PLEASE NOTE ON PLANS. IF APPLICABLE.
  
 10. CONDENSATE FOR TANKLESS NEEDS TO BE 1' AWAY FROM
 THE STRUCTURE PER THE 2020 FBC SEC. R318.5. IF
 APPLICABLE. WOULD YOU PLEASE NOTE ON PLANS. IF
 APPLICABLE.
  
 11. WOULD YOU PLEASE SHOW AND LABEL THE SHUTOFF VALVES
 AND DRIP LEGS ON GAS ISOMERIC PER THE 2020 FBC RES.
 SEC. G2420.5.
  
 12. WOULD YOU PLEASE SHOW COMPLIANCE FOR ELECTRICAL
 BONDING PER 2020 FGC 310/FBC RES G2411.
  
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 WEST PALM BEACH AMENDMENTS 2017 FBC CHAPTER; UPON
 REQUEST.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  