| Date |
Text |
| 2022-03-15 15:40:06 | 03/15/22 1ST GAS REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. WOULD YOU PLEASE SUBMIT THE ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS THE LENGTH OF ALL CUT SECTIONS OF PIPE |
| | PER 2020 FBC RES. SECS. G2413.4.1, G2413.4.2. INCLUDE |
| | PIPE LENGTHS, BTU LOADS, AND DISTANCES TO THE |
| | APPLIANCES THAT WERE USED TO CALCULATE MINIMUM PIPE |
| | SIZES USING THE SIZING TABLES FROM THE 2020 FGC 402/FBC |
| | RES G2413. (INCLUDE REFERENCES TO THE TABLE(S) USED) |
| | |
| | 2. THIS TANKLESS UNIT CALL FOR A 10.5? WATER COLUMN, |
| | AND THE SERVICE METER DISCHARGES IS A 12" WATER COLUMN |
| | REQUIRING A REGULATOR FOR THIS UNIT AS PER THE |
| | MANUFACTURER'S SPECIFICATION. SUBMIT MANUFACTURER'S |
| | SPECIFICATIONS FOR THE PRESSURE REGULATORS IF |
| | APPLICABLE. REGULATORS INSTALLED ON THE EXTERIOR OF THE |
| | BUILDING SHALL BE APPROVED FOR OUTDOOR INSTALLATION PER |
| | THE 2020 FBC RES. SEC. G2421.1 OR 410.1. |
| | |
| | 3. SHOW THE DISTANCE FROM THE POINT OF DELIVERY (GAS |
| | METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER THE 2020 FBC |
| | FG SEC. 402.4.1 OR 2020 FBC RES. SEC. G2413.4.1. |
| | |
| | |
| | 4. WOULD YOU PLEASE PROVIDE WHAT TYPE OF GAS (LP OR |
| | NATURAL) IS BEING USED PER THE WPB AMENDMENTS TO THE |
| | FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 5. INDICATE THE SYSTEM'S DELIVERY PRESSURE (PSI) ON THE |
| | PLAN PER THE 2020 FBC FG SEC. 402.2 OR 2020 FBC RES. |
| | SEC. G2413.2. |
| | |
| | 6. WOULD YOU PLEASE PROVIDE MANUFACTURES SPECIFICATIONS |
| | FOR GAS TANKLESS, GRILL BBQ, RANGE, FIREPLACE, AND GAS |
| | LIGHTS EQUIPMENT TO VERIFY COMPLIANCE WITH 2020 FBC |
| | RES. SEC. G2408.1. GAS APPLIANCES SHALL BE LISTED AND |
| | LABELED. THE INSTALLATION MANUALS FOR ALL GAS |
| | APPLIANCES/EQUIPMENT SHALL BE ONSITE AT THE TIME OF |
| | INSPECTION PER THE 2020 FBC RES. SEC. G2413.2 AND |
| | G2404.3. |
| | |
| | 7. IF UTILITIES PROVIDE A REGULATOR, NO SPECIFICATIONS |
| | ARE REQUIRED BUT SUBMIT THE MANUFACTURER'S |
| | SPECIFICATIONS FOR THE PRESSURE REGULATORS INSTALLED AT |
| | TANKLESS OR ANY OTHER LOCATION. REGULATORS INSTALLED ON |
| | THE EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR |
| | OUTDOOR INSTALLATION PER THE 2020 FBC RES. SEC. |
| | G2421.1. A REGULATOR IS REQUIRED TO BRING THE SYSTEM |
| | DOWN TO 10.5 WC ON THE HEART, BUT THE FPU REGULATOR MAY |
| | STEP DOWN FOR THIS SYSTEM. |
| | |
| | 8. WOULD YOU PLEASE SHOW ON THE HOUSE PLAN THE LOCATION |
| | OF THE TANK-LESS WATER HEATER AND THE LOCATION AND |
| | DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN RELATION |
| | TO THE WATER HEATER? THE LOCATION OF THE WATER HEATER |
| | SHALL COMPLY WITH THE MANUFACTURER'S INSTALLATION |
| | INSTRUCTIONS. THE HOUSE PLAN CAN BE HAND-DRAWN PER THE |
| | WPB AMENDMENTS TO THE FBC SEC. 107.2.1. INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | 9. HOT WATER LINES NOT IN CONDITION SPACE NEED TO BE |
| | INSULATED WITH A MINIMUM R-3 PER THE 2020 FBC SEC. RE |
| | 403.5.3. WOULD YOU PLEASE NOTE ON PLANS. IF APPLICABLE. |
| | |
| | 10. CONDENSATE FOR TANKLESS NEEDS TO BE 1' AWAY FROM |
| | THE STRUCTURE PER THE 2020 FBC SEC. R318.5. IF |
| | APPLICABLE. WOULD YOU PLEASE NOTE ON PLANS. IF |
| | APPLICABLE. |
| | |
| | 11. WOULD YOU PLEASE SHOW AND LABEL THE SHUTOFF VALVES |
| | AND DRIP LEGS ON GAS ISOMERIC PER THE 2020 FBC RES. |
| | SEC. G2420.5. |
| | |
| | 12. WOULD YOU PLEASE SHOW COMPLIANCE FOR ELECTRICAL |
| | BONDING PER 2020 FGC 310/FBC RES G2411. |
| | |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| | |
| | WEST PALM BEACH AMENDMENTS 2017 FBC CHAPTER; UPON |
| | REQUEST. |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |