2022-04-09 07:59:48FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) OUTLETS AT FRONT AND REAR OF BUILDING MISSING 210.52
  
 2) OUTLET SPACING IN SEVERAL ROOMS DOES NOT MEET 210.52
  
 3) BATHROOM OUTLETS MISSING 201.52
  
 210.52(A)(2) WALL SPACE. AS USED IN THIS SECTION, A
 WALL SPACE SHALL INCLUDE THE FOLLOWING:
 (1) ANY SPACE 600 MM (2 FT) OR MORE IN WIDTH
 (INCLUDINGSPACE MEASURED AROUND CORNERS) AND UNBROKEN
 ALONG THE
 FLOOR LINE BY DOORWAYS AND SIMILAR OPENINGS,
 FIREPLACES, AND FIXED CABINETS THAT DO NOT HAVE
 COUNTERTOPS OR SIMILAR
 WORK SURFACES
  
 210.52(D) BATHROOMS. AT LEAST ONE RECEPTACLE OUTLET
 SHALL BE INSTALLED IN BATHROOMS WITHIN 900 MM (3 FT) OF
 THE OUTSIDE EDGE OF
 EACH BASIN. THE RECEPTACLE OUTLET SHALL BE LOCATED ON A
 WALL OR PARTITION THAT IS ADJACENT TO THE BASIN OR
 BASIN COUNTERTOP, LOCA?
 TED ON THE COUNTERTOP, OR INSTALLED ON THE SIDE OR FACE
 OF THE BASIN CABINET. IN NO CASE SHALL THE RECEPTACLE
 BE LOCATED MORE
 THAN 300 MM (12 IN.) BELOW THE TOP OF THE BASIN OR
 BASIN COUNTERTOP. RECEPTACLE OUTLET ASSEMBLIES LISTED
 FOR USE IN COUNTERTOPS
 SHALL BE PERMITTED TO BE INSTALLED IN THE COUNTERTOP.
  
 210.52(E)(1) ONE-FAMILY AND TWO-FAMILY DWELLINGS. FOR A
 ONE-FAMILY DWELLING AND EACH UNIT OF A TWO-FAMILY
 DWELLING THAT IS AT GRADE
 LEVEL, AT LEAST ONE RECEPTACLE OUTLET READILY
 ACCESSIBLE FROM GRADE AND NOT MORE THAN 2.0 M (6 1?2
 FT) ABOVE GRADE LEVEL SHALL
 BE INSTALLED AT THE FRONT AND BACK OF THE DWELLING.
  
 FBC R315.1 CARBON MONOXIDE PROTECTION. EVERY SEPARATE
 BUILDING OR AN ADDITION TO AN EXISTING BUILDING FOR
 WHICH A PERMIT
 FOR NEW CONSTRUCTION IS ISSUED AND HAVING A
 FOSSIL-FUEL-BURNING HEATER OR APPLIANCE, A FIREPLACE,
 AN ATTACHED GARAGE, OR
 OTHER FEATURE, FIXTURE, OR ELEMENT THAT EMITS CARBON
 MONOXIDE AS BYPRODUCT OF COMBUSTION SHALL HAVE AN
 OPERATIONAL CARBON
 MONOXIDE ALARM INSTALLED WITHIN 10 FEET OF EACH ROOM
 USED FOR SLEEPING PURPOSES.
  
  