| 2022-03-17 13:46:00 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | 1) THERE IS AN INDICATION ON THE APPLICATION OF REPAIR |
| | INSULATION, DRYWALL, TILE, BASE TRIM & CABINETRY; |
| | HOWEVER, THE SUBMITTED PLAN SHEET INDICATES INSULATION |
| | & DRYWALL. |
| | |
| | PER NFPA 1 |
| | |
| | 1.7.12.7 PLANS SHALL BE SUBMITTED TO THE AHJ FOR OTHER |
| | CONDITIONS |
| | AS DEEMED NECESSARY BY THE AHJ TO DETERMINE COMPLIANCE |
| | WITH THE APPLICABLE CODES AND STANDARDS. |
| | |
| | FOR THE OFFICIAL RECORD AND CLARIFICATION PLEASE |
| | PROVIDE THE APPLICABLE CORRECT SCOPE OF WORK ON THE |
| | PLAN SHEET, INCLUDING TYPE OF TILE AND CABINET TYPE AND |
| | LOCATION. |
| | |
| | 2) THE PLAN SHEET INDICATES ONLY A LAUNDRY ROOM AND |
| | KITCHEN. |
| | |
| | 1.7.12.7 PLANS SHALL BE SUBMITTED TO THE AHJ FOR OTHER |
| | CONDITIONS |
| | AS DEEMED NECESSARY BY THE AHJ TO DETERMINE COMPLIANCE |
| | WITH THE APPLICABLE CODES AND STANDARDS. |
| | |
| | FOR THE OFFICIAL RECORD AND CLARIFICATION PLEASE |
| | INCLUDE THE TOTAL UNIT/APT FLOOR PLAN WITH THE AREA OF |
| | WORK HIGHLIGHTED. |
| | |
| | A WALL LOCATED ALONG A TENANT SEPARATION/CORRIDOR WALL |
| | SHALL BE MAINTENANCED AND REPAIRED TO THE EXISTING FIRE |
| | RATING OF THAT WALL. |
| | |
| | ENSURE COMPLIANCE AND PROVIDE AN APPLICABLE NOTE OF |
| | ACKNOWLEDGMENT. |
| | |
| | |
| | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |