Plan Review Notes
Plan Review Notes For Permit 22030531
Permit Number 22030531
Review Stop G
Sequence Number 2
Notes
Date Text
2022-05-25 08:26:212ND REVIEW FBC-2020 RES. GAS
 PERMIT- 22030531
 5/25/2022
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. THE REQUESTED
 MANUFACTURER?S SPECIFCATIONS FOR THE DRYER IN THE GUEST
 HOUSE WERE NOT SUBMITTED. PLEASE REVIEW 1ST REVIEW
 COMMENT BELOW AND COMPLY
  
 1) FAILED. G.1: PLEASE SUBMIT MANUFACTURERS
 SPECIFICATIONS FOR THE GAS DRYER- SEC. G2439.1 FBC RES.
 MAKE UP AIR SHALL BE PROVIDED IN ACCORDANCE WITH THE
 MANUFACTURER'S SPECIFICATIONS. THE PLAN APPEARS TO SHOW
 THE DRYER WILL BE INSTALLED IN A HALLWAY OPEN TO THE
 BEDROOM WHICH IS PROHIBITED PER SEC. G2406.2 FBC RES.
 GAS. THE DRYER IS ALLOWED TO BE INSTALLED IF MEETING
 EXCEPTION #5- THE DRYER SHALL BE ENCLOSED WITH A SOLID
 WEATHER- STRIPPED DOOR EQUIPPED WITH A SELF CLOSING
 DEVICE. ALL COMBUSTION AIR SHALL BE TAKEN DIRECTLY FROM
 THE OUTDOORS IN ACCORDANCE WITH SEC. G2407.6. AS AN
 ALTERNATIVE TO MEETING THE FUEL GAS CODE REQUIREMENTS
 PROVIDE AN ELECTRIC DRYER.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  