| 2022-05-25 08:26:21 | 2ND REVIEW FBC-2020 RES. GAS |
| | PERMIT- 22030531 |
| | 5/25/2022 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. THE REQUESTED |
| | MANUFACTURER?S SPECIFCATIONS FOR THE DRYER IN THE GUEST |
| | HOUSE WERE NOT SUBMITTED. PLEASE REVIEW 1ST REVIEW |
| | COMMENT BELOW AND COMPLY |
| | |
| | 1) FAILED. G.1: PLEASE SUBMIT MANUFACTURERS |
| | SPECIFICATIONS FOR THE GAS DRYER- SEC. G2439.1 FBC RES. |
| | MAKE UP AIR SHALL BE PROVIDED IN ACCORDANCE WITH THE |
| | MANUFACTURER'S SPECIFICATIONS. THE PLAN APPEARS TO SHOW |
| | THE DRYER WILL BE INSTALLED IN A HALLWAY OPEN TO THE |
| | BEDROOM WHICH IS PROHIBITED PER SEC. G2406.2 FBC RES. |
| | GAS. THE DRYER IS ALLOWED TO BE INSTALLED IF MEETING |
| | EXCEPTION #5- THE DRYER SHALL BE ENCLOSED WITH A SOLID |
| | WEATHER- STRIPPED DOOR EQUIPPED WITH A SELF CLOSING |
| | DEVICE. ALL COMBUSTION AIR SHALL BE TAKEN DIRECTLY FROM |
| | THE OUTDOORS IN ACCORDANCE WITH SEC. G2407.6. AS AN |
| | ALTERNATIVE TO MEETING THE FUEL GAS CODE REQUIREMENTS |
| | PROVIDE AN ELECTRIC DRYER. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |