Plan Review Notes
Plan Review Notes For Permit 22030526
Permit Number 22030526
Review Stop P
Sequence Number 1
Notes
Date Text
2022-04-05 14:05:14CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 22030526 295 LAKEVIEW AVE
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
 A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS
 REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW
 PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL
 PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST
 BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW
 APPROVAL.
  
 1. REGARDING A2.01/SCOPE OF DEMOLITION NOTE 13, PER WPB
 FBC 107.2.1, TO SHOW COMPLIANCE WITH FBC ACC CHAPTERS
 2, 3 AND 6 PROVIDE DETAILS OR NOTES FOR REFINISHED
 TOILET ROOMS INDICATING THE FOLLOWING:
 ***A) THE WATER CLOSET SHALL BE POSITIONED WITH A WALL
 OR PARTITION TO THE REAR AND TO ONE SIDE. THE
 CENTERLINE OF THE WATER CLOSET SHALL BE 16 INCHES
 MINIMUM TO 18 INCHES MAXIMUM FROM THE SIDE WALL OR
 PARTITION PER FBC ACC 604.2
 ***B) CLEARANCE AROUND A WATER CLOSET SHALL BE 60
 INCHES MINIMUM MEASURED PERPENDICULAR FROM THE SIDE
 WALL AND 56 INCHES DEEP MINIMUM FOR WALL HUNG WATER
 CLOSETS AND 59 INCHES DEEP MINIMUM FOR FLOOR MOUNTED
 WATER CLOSETS MEASURED PERPENDICULAR TO THE REAR
 WALL.PER FBC ACC 604.3.1 AND 604.8.1.1.
 ***C) THE SIDE WALL GRAB BAR SHALL BE 42 INCHES LONG
 MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM FROM THE
 REAR WALL AND EXTENDING 54 INCHES MINIMUM FROM THE REAR
 WALL PER FBC ACC 604.5.1
 ***D) THE REAR WALL GRAB BAR SHALL BE 36 INCHES LONG
 MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER
 CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24 INCHES
 MINIMUM ON THE OTHER SIDE PER FBC ACC 604.5.2
 ***E) FLUSH CONTROLS SHALL BE HAND OPERATED OR
 AUTOMATIC. HAND OPERATED FLUSH CONTROLS SHALL COMPLY
 WITH 309. FLUSH CONTROLS SHALL BE LOCATED ON THE OPEN
 SIDE OF THE WATER CLOSET PER FBC ACC 604.6
 ***F) TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4
 AND SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN
 FRONT OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF
 THE DISPENSER. THE OUTLET OF THE DISPENSER SHALL BE 15
 ***G) INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE
 FINISH FLOOR AND SHALL NOT BE LOCATED BEHIND GRAB BARS
 PER FBC ACC 604.8.
 ***H) THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE
 FINISH FLOOR SHALL BE 17 INCHES MINIMUM AND 19 INCHES
 MAXIMUM MEASURED TO THE TOP OF THE SEAT. SEATS SHALL
 NOT BE SPRUNG TO RETURN TO A LIFTED POSITION PER FBC
 ACC 604.4.
 ***I) PER FBC ACC 609.4, GRAB BARS SHALL BE INSTALLED
 IN A HORIZONTAL POSITION, 33 INCHES MINIMUM AND 36
 INCHES MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE
 TOP (NOT THE CENTER) OF THE GRIPPING SURFACE.
 ***J) URINALS SHALL BE THE STALL-TYPE OR THE WALL-HUNG
 TYPE WITH THE RIM 17 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND. URINALS SHALL BE 13 1/2 INCHES DEEP
 MINIMUM MEASURED FROM THE OUTER FACE OF THE URINAL RIM
 TO THE BACK OF THE FIXTURE PER FBC ACC 605.2
 ***K) LAVATORIES SHALL BE INSTALLED WITH THE FRONT OF
 THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND PER FBC ACC
 606.3, ADDITIONALLY TOE AND KNEE CLEARANCE SHALL BE AS
 REQUIRED BY FBC ACC 306.2 AND 306.3
 ***L) PER FBC 606.5 EXPOSED PIPES AND SURFACES. WATER
 SUPPLY & DRAINPIPES UNDER LAVATORIES AND SINKS SHALL BE
 INSULATED OR OTHERWISE CONFIGURED TO PROTECT AGAINST
 CONTACT.
 ***M) UNITS SHALL HAVE A CLEAR FLOOR OR GROUND SPACE
 COMPLYING WITH 305 POSITIONED FOR A FORWARD APPROACH
 AND CENTERED ON THE UNIT. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED PER FBC ACC 602.2.
 ***N) MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS
 SHALL BE INSTALLED WITH THE BOTTOM EDGE OF THE
 REFLECTING SURFACE 40 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND. MIRRORS NOT LOCATED ABOVE LAVATORIES
 OR COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE
 OF THE REFLECTING SURFACE 35 INCHES MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND PER FBC ACC 603.3.
  
 2. IS THERE A CHANGE OF OCCUPANCY? PER WPB FBC 107.2.1,
 PROVIDE OCCUPANCY AND LOAD.
  
 3. PER WPB FBC 107.2.1, PROVIDE PLUMBING FIXTURE
 SCHEDULE (INCLUSIVE OF ALL NEW AND EXISTING FIXTURES)
 SHOWING COMPLIANCE WITH OCCUPANCY TYPE ACCORDING TO FBC
 PL 403.1 AND TABLE 403. PLEASE NOTE, A SERVICE SINK IS
 PROBABLY A REQUIREMENT. IF THERE IS AN EXISTING SERVICE
 SINK, PLEASE INDICATE ON THE PLANS. IF NOT, PROVIDE AS
 WOULD BE REQUIRED BY FBC PL TABLE 403.1.
  
 4. RE: PFL-1.1/PLUMBING DEMOLITION KEY NOTE 4, PER WPB
 FBC 107.2.1, PROVIDE THE FOLLOWING:
 ***A) PLAN SHEET NUMBER SHOWING THE NEW LOCATION OF THE
 HOSE BIBB
 ***B) PLAN VIEW ROUTING AND RISER DIAGRAM OF EXTENDED
 PIPING; PROVIDE SIZE AND MATERIAL TYPE.
 ***C) PROVIDE A VACUUM BREAKER PER FBC PL 608.1/TABLE
 608.1.
 ***D) PROVIDE A SHUTOFF VALVE PER FBC PL 606.2(2).
 ***E) PROVIDE A HANGER DETAIL WITH A NOTE STATING,
 "HORIZONTAL PIPE SHALL BE SUPPORTED IN ACCORDANCE WITH
 FBC PL TABLE 308.5."
  
 5. PER WPB FBC 107.2.1, PROVIDE TYPICAL DETAIL FOR
 CAPPING OF ABANDONED PLUMBING PIPING (SANITARY DRAINS,
 VENTS AND WATER)
  
 6. PER WPB FBC 107.2.1, PROVIDE A SLAB REPAIR DETAIL ON
 THE PLANS FOR THE PLUMBING WORK THAT IS TO BE REMOVED
 AND CAPPED BELOW THE FLOOR AS NOTED ON PFL-1.1 AND
 A2.01. SHOW THE WIDTH OF THE REPAIR, THE MINIMUM
 THICKNESS AND PSI OF THE CONCRETE TO BE REPLACED. SHOW
 SIZE, LENGTH, SPACING (ON CENTER), MINIMUM EMBEDMENT
 AND ANCHORING/ADHESIVE MATERIAL FOR DOWELS. THE REPAIR
 SHALL ALSO INCLUDE TERMITE TREATMENT OF THE SOIL AS
 WELL AS THE REQUIRED VAPOR BARRIER OVER WELL COMPACTED
 SOIL. A COPY OF THE TERMITE CERTIFICATE SHALL BE ONSITE
 FOR FINAL INSPECTION.
  
 7. ALL COMPONENTS IN THE DOMESTIC WATER SYSTEM SHALL BE
 LEAD FREE IN ACCORDANCE WITH FBC PL 605.2 AND 605.2.1.
 PER WPB FBC 107.2.1, PROVIDE NOTE ON PLANS STATING THE
 SAME.
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER PX928
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  