Date Text
2022-03-17 16:07:05THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) SHEET AO .01 - THERE ARE INDICATIONS OF NO FIRE
 ALARM OR FIRE SPRINKLER REVISIONS AS PART OF THIS WORK.
  
 HOWEVER, UNDER THE SCOPE OF WORK FOR EACH FLOOR THERE
 ARE INDICATIONS OF WORK THAT MAY AFFECT FIRE ALARM &
 FIRE SPRINKLER EQUIPMENT.
  
 THE FIRE SPRINKLER & FIRE ALARM SYSTEMS SHALL BE
 MAINTAINED THROUGHOUT DEMO & CONSTRUCTION PERIODS
  
 ANY WORK ON THE FIRE SPRINKLER & FIRE ALARM, INCLUDING
 DEMO, SHALL BE DONE UNDER SEPARATE PERMITS & SHOP
 DRAWINGS.
  
 PLEASE PROVIDE A NOTE OF ACKNOWLEDGMENT ON THE PLAN
 SHEET.
  
  
 1A) PER THE ABOVE FIRE ALARM COMMENT, HOW WILL THE FIRE
 ALARM BE MAINTAINED WHILE WORK IS BEING DONE ON EACH
 FLOOR.
  
 PLEASE INCLUDE SPECIFIC DETAILS INCLUDING HOW FALSE
 ALARMS WILL BE CONTROLLED.
  
  
 1B) PER THE ABOVE FIRE SPRINKLER COMMENT, HOW WILL THE
 FIRE SPRINKLER HEADS BE MAINTAINED WHILE WORK IS BEING
 DONE ON EACH FLOOR.
  
 PLEASE INCLUDE SPECIFIC DETAILS.
  
  
 1C) THE REASON FOR COMMENTS 1A & 1B IS THAT THE FIRE
 ALARM & FIRE SPRKLER CONTRACTOR WILL NEED TO BE
 INVLOVED HOW HOW THES SYSTEMS AND EQUIPMENT WILL REMAIN
 FUNCTIONAL AND IS DAMAGE REAPIRED UNDER SEPARATE PEMRIS
 AND SHOP DRAWINGS.
  
  
 2) A SHEET - UNDER THE SCOPE OF WORK THERE ARE
 INDICATIONS OF CLOSING OFF A FLOOR FOR GUESTS TO
 COMPLETE THE WORK UNTIL MOVING TO ANOTHER FLOOR.
  
 THERE ARE NO INDICATIONS HOW THIS WILL TAKE PLACE.
  
 HOW WILL THE FLOOR AREA, INCLUDING STAIR AND ELEVATOR,
 BE ISOLATED SO THAT GUESTS CAN NOT ENTER THE
 CONSTRUCTION AREA AND STILL ALLOW ACCESS/EGRESS TO
 WORKERS?
  
 PLEASE PROVIDE A DETAILED LIFE SAFETY PLAN.
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  