| Date |
Text |
| 2022-03-17 16:07:05 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | 1) SHEET AO .01 - THERE ARE INDICATIONS OF NO FIRE |
| | ALARM OR FIRE SPRINKLER REVISIONS AS PART OF THIS WORK. |
| | |
| | HOWEVER, UNDER THE SCOPE OF WORK FOR EACH FLOOR THERE |
| | ARE INDICATIONS OF WORK THAT MAY AFFECT FIRE ALARM & |
| | FIRE SPRINKLER EQUIPMENT. |
| | |
| | THE FIRE SPRINKLER & FIRE ALARM SYSTEMS SHALL BE |
| | MAINTAINED THROUGHOUT DEMO & CONSTRUCTION PERIODS |
| | |
| | ANY WORK ON THE FIRE SPRINKLER & FIRE ALARM, INCLUDING |
| | DEMO, SHALL BE DONE UNDER SEPARATE PERMITS & SHOP |
| | DRAWINGS. |
| | |
| | PLEASE PROVIDE A NOTE OF ACKNOWLEDGMENT ON THE PLAN |
| | SHEET. |
| | |
| | |
| | 1A) PER THE ABOVE FIRE ALARM COMMENT, HOW WILL THE FIRE |
| | ALARM BE MAINTAINED WHILE WORK IS BEING DONE ON EACH |
| | FLOOR. |
| | |
| | PLEASE INCLUDE SPECIFIC DETAILS INCLUDING HOW FALSE |
| | ALARMS WILL BE CONTROLLED. |
| | |
| | |
| | 1B) PER THE ABOVE FIRE SPRINKLER COMMENT, HOW WILL THE |
| | FIRE SPRINKLER HEADS BE MAINTAINED WHILE WORK IS BEING |
| | DONE ON EACH FLOOR. |
| | |
| | PLEASE INCLUDE SPECIFIC DETAILS. |
| | |
| | |
| | 1C) THE REASON FOR COMMENTS 1A & 1B IS THAT THE FIRE |
| | ALARM & FIRE SPRKLER CONTRACTOR WILL NEED TO BE |
| | INVLOVED HOW HOW THES SYSTEMS AND EQUIPMENT WILL REMAIN |
| | FUNCTIONAL AND IS DAMAGE REAPIRED UNDER SEPARATE PEMRIS |
| | AND SHOP DRAWINGS. |
| | |
| | |
| | 2) A SHEET - UNDER THE SCOPE OF WORK THERE ARE |
| | INDICATIONS OF CLOSING OFF A FLOOR FOR GUESTS TO |
| | COMPLETE THE WORK UNTIL MOVING TO ANOTHER FLOOR. |
| | |
| | THERE ARE NO INDICATIONS HOW THIS WILL TAKE PLACE. |
| | |
| | HOW WILL THE FLOOR AREA, INCLUDING STAIR AND ELEVATOR, |
| | BE ISOLATED SO THAT GUESTS CAN NOT ENTER THE |
| | CONSTRUCTION AREA AND STILL ALLOW ACCESS/EGRESS TO |
| | WORKERS? |
| | |
| | PLEASE PROVIDE A DETAILED LIFE SAFETY PLAN. |
| | |
| | |
| | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |