Notes
Date Text
2022-04-01 14:09:5104/01/22 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. ON SHEET C-1, UNDER GENERAL NOTES, IT MENTIONS THE
 6TH EDITION, AND THE RECENT ADDITION IS THE 2020 FBC
 7TH EDITION. WOULD YOU PLEASE CORRECT PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 2. ON SHEET 1.0A;
  
 A. WOULD YOU PLEASE GIVE DIMENSIONS FOR FIXTURE
 CLEARANCES FOR WATER CLOSET LAV AND TURNING RADIUS PER
 FLORIDA BUILDING CODE AND FLORIDA ACCESSIBILITY CODE.
  
 B. ADA DETAIL OF HEIGHTS AND DIMENSIONS NOT SHOWN;
 PLEASE PROVIDE DETAILED DRAWINGS PER THE 2020 FBC
 ACCESSIBILITY CODE.
  
 3. ON SHEET 1.3A, THE SERVICE SINK (MOP SINK)
 SURROUNDING THE WALL SHALL BE A NON-ABSORBENT SURFACE
 IN ACCORDANCE WITH THE 2020 FBC BUILDING SEC. 1210.2.2
 AND 2020 FBC SEC. P 310.3. THE PAINT IS NOT AN APPROVED
 FINISH. PLEASE MAKE A NOTE ON THIS SHEET.
  
 4. ON SHEET 3.2P;
  
 A. IT SHOWS A TWO HAND SINK GOING INTO THE GREASE
 INTERCEPTOR. IT SHALL NOT GO INTO GREASE INTERCEPTORS
 AS THEY DO NOT PRODUCE WASTE REQUIRING TREATMENT OR
 SEPARATION AND SHALL BE DISCHARGED INTO ANY INTERCEPTOR
 PER THE 2020 FBC SEC. 1003.2 APPROVAL.
  
 B. IN THE ISOMETRIC, IT SHOWS THE ICE LINE AND WATER
 GOING INTO SANITARY, AND ON 3.0P, IT SHOWS IT GOING IN
 INTO GREASE, AND IT IS LABELED AS A WATER CLOSET. IT
 NEEDS TO SHOW GOING INTO THE SANITARY. WOULD YOU PLEASE
 CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 C. ICEMAKER AND COFFEE MAKER SHALL BE EQUIPPED WITH AN
 IN-LINE VACUUM BREAKER THAT COMPLIES WITH ASSE 1024 PER
 THE 2020 FBC SEC. 608.13.10.
  
 5. DUE TO A CHANGE IN PROCESS, THE BACKFLOW PERMIT AND
 GREASE INTERCEPTOR PERMITS MUST BE SUBMITTED BEFORE
 ISSUING THE PRIMARY PERMIT (AS APPLICABLE). YOU CAN
 SUBMIT AN APPLICATION "TBD" (TO BE DETERMINED) IF YOU
 DO NOT HAVE A CONTRACTOR SELECTED BY EMAILING A
 COMPLETED PERMIT APPLICATION TO [email protected]
 . YOU WILL RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD
 PLANS. YOU MAY UPLOAD PLANS AND PAY FEES AT A FUTURE
 DATE, BUT THE APPLICATION IS REQUIRED AT THIS TIME. WE
 RECOMMEND THAT YOU PAY FEES AND UPLOAD PLANS AT THE
 SAME TIME. AFTER YOU HAVE THE PERMIT(S) GENERATED,
 NOTIFY ME VIA EMAIL, AND I WILL CHANGE THE REVIEW
 STATUS TO PASS.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 WEST PALM BEACH AMENDMENTS 2017 FBC CHAPTER; UPON
 REQUEST.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  