| 2022-04-01 14:09:51 | 04/01/22 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. ON SHEET C-1, UNDER GENERAL NOTES, IT MENTIONS THE |
| | 6TH EDITION, AND THE RECENT ADDITION IS THE 2020 FBC |
| | 7TH EDITION. WOULD YOU PLEASE CORRECT PER THE WPB |
| | AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | 2. ON SHEET 1.0A; |
| | |
| | A. WOULD YOU PLEASE GIVE DIMENSIONS FOR FIXTURE |
| | CLEARANCES FOR WATER CLOSET LAV AND TURNING RADIUS PER |
| | FLORIDA BUILDING CODE AND FLORIDA ACCESSIBILITY CODE. |
| | |
| | B. ADA DETAIL OF HEIGHTS AND DIMENSIONS NOT SHOWN; |
| | PLEASE PROVIDE DETAILED DRAWINGS PER THE 2020 FBC |
| | ACCESSIBILITY CODE. |
| | |
| | 3. ON SHEET 1.3A, THE SERVICE SINK (MOP SINK) |
| | SURROUNDING THE WALL SHALL BE A NON-ABSORBENT SURFACE |
| | IN ACCORDANCE WITH THE 2020 FBC BUILDING SEC. 1210.2.2 |
| | AND 2020 FBC SEC. P 310.3. THE PAINT IS NOT AN APPROVED |
| | FINISH. PLEASE MAKE A NOTE ON THIS SHEET. |
| | |
| | 4. ON SHEET 3.2P; |
| | |
| | A. IT SHOWS A TWO HAND SINK GOING INTO THE GREASE |
| | INTERCEPTOR. IT SHALL NOT GO INTO GREASE INTERCEPTORS |
| | AS THEY DO NOT PRODUCE WASTE REQUIRING TREATMENT OR |
| | SEPARATION AND SHALL BE DISCHARGED INTO ANY INTERCEPTOR |
| | PER THE 2020 FBC SEC. 1003.2 APPROVAL. |
| | |
| | B. IN THE ISOMETRIC, IT SHOWS THE ICE LINE AND WATER |
| | GOING INTO SANITARY, AND ON 3.0P, IT SHOWS IT GOING IN |
| | INTO GREASE, AND IT IS LABELED AS A WATER CLOSET. IT |
| | NEEDS TO SHOW GOING INTO THE SANITARY. WOULD YOU PLEASE |
| | CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | C. ICEMAKER AND COFFEE MAKER SHALL BE EQUIPPED WITH AN |
| | IN-LINE VACUUM BREAKER THAT COMPLIES WITH ASSE 1024 PER |
| | THE 2020 FBC SEC. 608.13.10. |
| | |
| | 5. DUE TO A CHANGE IN PROCESS, THE BACKFLOW PERMIT AND |
| | GREASE INTERCEPTOR PERMITS MUST BE SUBMITTED BEFORE |
| | ISSUING THE PRIMARY PERMIT (AS APPLICABLE). YOU CAN |
| | SUBMIT AN APPLICATION "TBD" (TO BE DETERMINED) IF YOU |
| | DO NOT HAVE A CONTRACTOR SELECTED BY EMAILING A |
| | COMPLETED PERMIT APPLICATION TO [email protected] |
| | . YOU WILL RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD |
| | PLANS. YOU MAY UPLOAD PLANS AND PAY FEES AT A FUTURE |
| | DATE, BUT THE APPLICATION IS REQUIRED AT THIS TIME. WE |
| | RECOMMEND THAT YOU PAY FEES AND UPLOAD PLANS AT THE |
| | SAME TIME. AFTER YOU HAVE THE PERMIT(S) GENERATED, |
| | NOTIFY ME VIA EMAIL, AND I WILL CHANGE THE REVIEW |
| | STATUS TO PASS. |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| | |
| | WEST PALM BEACH AMENDMENTS 2017 FBC CHAPTER; UPON |
| | REQUEST. |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |